Chapter V

Firestop, Fireproofing, and Smoke Containment

Red Seal Practice study guide with diagrams.

Fire Stops, Fireproofing, and Smoke Containment

Chapter Introduction

This chapter covers passive fire protection systems, a distinct field from active protection (sprinklers, alarms). As a heat and frost insulator, you will be called upon to install, repair, or replace insulating materials in buildings where compartmentation and fire resistance requirements are critical. The National Building Code of Canada (NBCC) and Canadian Standards Association (CSA) standards govern this work. Your role is not limited to installing thermal insulation; you must understand how your materials interact with fire stop systems and how to preserve the integrity of fire barriers during your interventions.


1. Fundamental Definitions

1.1 Fire Resistance (FR)

Fire resistance is the ability of a building element to withstand exposure to fire for a specified duration while continuing to perform its structural and separation functions. It is expressed in minutes (45, 60, 90, 120, 180) and determined according to CAN/ULC-S101 (Fire Resistance Tests for Building Construction Materials).

Three criteria are evaluated simultaneously:

Stability (load-bearing capacity)
Integrity (passage of flames and hot gases)
Thermal insulation (temperature rise on the unexposed face)

1.2 Fire Resistance Rating (FRR)

The FRR is the rating assigned to a building element after testing. It is expressed in minutes and corresponds to the time during which the element satisfies the criteria above. For example, a wall with an FRR of 90 minutes will withstand a standard fire for 90 minutes before failure.

1.3 Fire Stop

A fire stop is a complete system (material + labour) installed in a penetration (opening) made in a fire barrier to allow the passage of services (piping, conduits, cables). It must restore the FRR of the barrier for a specified duration.

1.4 Fire Compartment

A fire compartment is a subdivision of a building bounded by elements having a minimum FRR, designed to limit the spread of fire and smoke. Heat and frost insulators must understand that every penetration in these compartments is a potential weakness.

1.5 Fireproofing

Fireproofing is the treatment of combustible materials (wood, steel, fabrics) to delay ignition and slow flame spread. For steel, fireproofing (intumescent paint or boards) aims to keep the steel temperature below the critical threshold of 538 °C (1000 °F) to preserve its load-bearing capacity.

1.6 Smoke Containment

Smoke containment is the set of measures designed to prevent the migration of toxic and hot smoke toward evacuation routes and adjacent compartments. Smoke is responsible for the majority of fire-related deaths. Smoke barriers, fire dampers, and fire-rated expansion joints play a crucial role.


2. Regulatory and Code Framework

2.1 National Building Code of Canada (NBCC)

The NBCC is published by the National Research Council of Canada (NRC). It is adopted, with or without modifications, by the provinces and territories. The relevant sections for the heat and frost insulator:

Section 3.1 : Combustible and non-combustible materials
Section 3.1.8 : Thermal insulation (requirements for protection against ignition)
Section 3.1.9 : Wood-frame construction (protection of insulation)
Section 3.6 : Building services (fire stop penetrations)
Section 3.6.4.2 : Penetration of fire separations by pipes and ducts
Section 3.6.4.3 : Penetration of fire separations by electrical cables

2.2 Material Classification Standards

StandardPurpose
**CAN/ULC-S101**Fire resistance tests for building construction materials
**CAN/ULC-S102**Flame spread and smoke development test (surface materials)
**CAN/ULC-S114**Determination of non-combustibility of materials
**CAN/ULC-S115**Fire stop test (penetrations)
**CAN/ULC-S134**Fire behaviour test for wall assemblies
**CAN/ULC-S703**Standard for fibreglass thermal insulation

2.3 Key NBCC Rules

Article 3.1.5.12 : Thermal insulation must be non-combustible or protected by a non-combustible material if the surface temperature may exceed 90 °C.

Article 3.1.5.14 : Thermal insulation made of plastic foam must be covered by a non-combustible material (gypsum, plaster) with a minimum thickness of 12.7 mm (½ in.).

Article 3.6.4.2 : Penetrations in fire separations must be protected by a fire stop system conforming to CAN/ULC-S115, with an F rating (fire resistance) at least equal to the FRR of the penetrated barrier.

Article 3.6.4.3 : Penetrations by electrical cables must be protected by fire stop systems tested according to CAN/ULC-S115, with an FT rating (fire resistance + smoke tightness).


3. Types of Fire Stop Materials

3.1 Sealants and Caulking

Fire stop sealants are paste-like products applied by gun or trowel. They are classified into two categories:

TypeFire BehaviourTypical Use
**Intumescent**Expands (×5 to ×30) under heat, forming a charred barrierPlastic pipe penetrations, cables
**Endothermic**Absorbs heat through chemical reaction (water release)Metallic pipe penetrations

3.2 Mortars and Lightweight Concretes

Fire stop mortars are dry mixes to be mixed with water. They offer high mechanical strength and are suitable for large openings. Their density ranges from 400 to 1200 kg/m³.

3.3 Boards and Blankets

Fire stop boards are manufactured from mineral wool (rock wool or slag wool) treated with binders. They are used for large openings, linear joints, and ducts. Their typical density is 100 to 200 kg/m³.

3.4 Fire Stop Pillows

Fire stop pillows are flexible blocks of encapsulated intumescent foam. They allow for rapid modifications (adding/removing cables) without special tools. They are reusable.

3.5 Intumescent Paints

Intumescent paints are applied to structural steel. Under heat, they expand to form an insulating charred layer. The dry film thickness is calculated based on the section factor (A/V) of the steel section.

3.6 Fire Stop Collars

Fire stop collars are metallic sleeves containing an intumescent insert. They are installed around plastic pipes passing through a barrier. In the event of a fire, the insert expands and crushes the pipe, sealing the opening.


4. Installation Principles and Procedures

4.1 Pre-Installation Assessment

Before any fire stop installation, you must:

58.Identify the type of barrier : wall (FRR), floor (FRR), building assembly
59.Identify the penetrating service : metallic pipe, plastic pipe, electrical conduit, cables, ventilation duct
60.Determine the size of the penetration : diameter, shape (circular, rectangular), annular space
61.Verify the required rating : F (fire), FT (fire + smoke), FH (fire + hydraulic shock)
62.Select the fire stop system : refer to the manufacturer's installation guide (tests are specific to each configuration)

4.2 Surface Preparation

Clean the surface around the penetration to remove dust, oil, grease, and moisture
Remove burrs and sharp edges
Verify that the substrate is sound and will adhere properly
The application temperature must conform to manufacturer specifications (generally between 4 °C and 38 °C)

4.3 Fire Stop Installation

General procedure for an intumescent sealant:

70.Install a backing material (mineral wool, foam) to fill the annular space if the opening is large
71.Apply the sealant continuously, without voids or air bubbles
72.Smooth the surface to ensure uniform thickness
73.Respect the minimum thickness specified in the installation guide (often 12.7 mm to 25.4 mm)
74.Allow to dry according to the indicated curing time (24 to 72 hours)

Procedure for a fire stop collar:

76.Slide the collar onto the pipe before inserting it through the barrier
77.Position the collar at the centre of the barrier (or according to instructions)
78.Tighten the fastening screws to ensure intimate contact with the pipe
79.Secure the collar to the structure if required

4.4 Marking and Documentation

Each fire stop installation must be identified by a label indicating:

The manufacturer and system number
The rating (F, FT, FH)
The installation date
The installer's name

This documentation is essential for future inspection and maintenance.


5. Calculations and Sizing Factors

5.1 Section Factor (A/V)

The section factor is the ratio of the exposed surface area of the steel (A, in m²) to its volume (V, in m³). It is expressed in m⁻¹. The higher this factor, the faster the steel heats up, and the thicker the protection must be.

Formula: A/V = (exposed perimeter) / (cross-sectional area)

Example: For a HEA 200 beam:

Exposed perimeter ≈ 0.8 m
Cross-sectional area ≈ 0.0064 m²
A/V = 0.8 / 0.0064 = 125 m⁻¹

5.2 Protection Thickness

The thickness of intumescent paint is determined from tables provided by the manufacturer, based on:

The section factor (A/V)
The required FRR (45, 60, 90, 120 minutes)
The critical steel temperature (often 538 °C)

General rule: The higher the A/V, the greater the required thickness. An increase in FRR from 60 to 120 minutes may require double the thickness.

5.3 Annular Space Calculation

The annular space is the distance between the pipe and the edge of the opening in the barrier.

Formula: Annular space = (opening diameter − pipe diameter) / 2

Example: 150 mm opening, 100 mm pipe:

Annular space = (150 − 100) / 2 = 25 mm

This space must be filled with the appropriate fire stop material. If the annular space exceeds the maximum tested value (often 50 mm), you must use additional backing material or a different system.

5.4 Calculating Pipe Coverage Length

For plastic pipes passing through a barrier, an exposed pipe length is required on each side of the barrier. This length, generally 300 to 600 mm, allows the pipe to melt and deform without pulling the collar out of the barrier.


6. Structural Steel Fireproofing

6.1 Why Fireproof Steel?

Steel loses its mechanical strength at high temperatures:

At 400 °C: 20% loss of yield strength
At 538 °C: 50% loss (standard critical threshold)
At 700 °C: 80% loss

The NBCC requires structural steel members to have a minimum FRR depending on the occupancy and building height (for example, 45 minutes for a 3-storey building, 120 minutes for a building over 12 storeys).

6.2 Fireproofing Methods

MethodAdvantagesDisadvantages
**Intumescent paint**Aesthetic, thin (0.5 to 5 mm)High cost, requires clean surface
**Rigid boards (mineral wool)**Mechanical strength, durableBulky, difficult for complex shapes
**Sprayed fibres (mineral wool)**Economical, fastRough surface, requires mechanical protection
**Sprayed concrete**Very resistant, fireproofHeavy, requires formwork for certain shapes

6.3 Intumescent Paint Application Procedure

121.Surface preparation : sandblasting or stripping to achieve adequate anchor profile (roughness)
122.Primer application : anti-corrosion coat compatible with the intumescent paint
123.Intumescent paint application : by spray, in multiple passes to achieve the required dry film thickness
124.Thickness verification : measurement with dry film thickness gauges (destructive or non-destructive)
125.Topcoat application : protective layer against moisture and UV

Critical point: The dry film thickness must be verified on every member. A 10% under-thickness can reduce the FRR by 20 to 30 minutes.


7. Smoke Containment

7.1 Smoke Barriers

Smoke barriers are vertical or horizontal assemblies designed to limit smoke migration. They do not necessarily have an FRR, but must be smoke-tight and have sufficient mechanical stability.

7.2 Fire Dampers and Smoke Dampers

Fire dampers are installed in ventilation ducts passing through fire separations. They close automatically at a temperature of 74 °C (165 °F) to prevent fire spread.

Smoke dampers close upon signal from the smoke detection system. They are tested according to UL 555S.

7.3 Fire-Rated Expansion Joints

Fire-rated expansion joints are installed in building expansion joints. They allow thermal and seismic movement while maintaining fire and smoke tightness. They are tested according to CAN/ULC-S115 with cyclic movement requirements.

7.4 The Heat and Frost Insulator's Role in Smoke Containment

When installing thermal insulation on piping passing through barriers, the heat and frost insulator must:

138.Never obstruct fire dampers with insulation
139.Maintain the required clearance around dampers (often 150 mm)
140.Restore the fire stop after any modification to the piping
141.Use non-combustible insulation in areas where temperatures may exceed 90 °C

8. Specific Requirements for Thermal Insulation

8.1 Insulation and Fire Resistance

The NBCC classifies thermal insulation into two categories:

CategoryExamplesRequirements
**Non-combustible**Fibreglass, rock wool, perlite, vermiculiteNo additional protection required
**Combustible**Polyurethane foam, polystyrene, polyisocyanurateMust be protected by a non-combustible material (gypsum, plaster) of at least 12.7 mm

8.2 Insulation on Piping Passing Through Fire Stops

When insulated piping passes through a fire barrier, the fire stop system must be designed to account for the insulation. The options are:

149.Remove the insulation over a length of 300 mm on each side of the barrier and install the fire stop directly on the pipe
150.Use a fire stop system tested with insulation (some manufacturers have assemblies tested with specific insulation thicknesses)
151.Install a fire stop sleeve sized for the outer diameter of the insulation

Caution: Insulation can act as a wick, spreading fire along the pipe. CAN/ULC-S115 tests include configurations with and without insulation.

8.3 Protection of Plastic Foam Insulation

Plastic foam insulation (polyurethane, polystyrene) is combustible and produces toxic smoke. The NBCC requires:

Article 3.1.5.14 : Protection by a non-combustible material at least 12.7 mm thick
Article 3.1.5.15 : Foam insulation must have a maximum flame spread rating of 25 and a maximum smoke development rating of 500 (according to CAN/ULC-S102)

9. Inspection and Maintenance Procedures

9.1 Visual Inspection

Fire stop inspection must be carried out:

After any modification or repair
During periodic building inspections (annual or semi-annual)
After a fire or water damage

Points to check:

Absence of cracks, voids, or delamination
Adequate material thickness
Labels in place and legible
Absence of unauthorized modifications

9.2 Fire Stop Repair

Repairs must use the same system as the original, or an equivalent system tested for the same configuration. It is prohibited to mix products from different manufacturers without validation by testing.

9.3 Documentation

The fire stop register must include:

Location of each fire stop (floor, room, coordinates)
System type and manufacturer
Installation and inspection dates
Inspection results and repairs performed

10. Pitfalls to Avoid

179.Confusing fire resistance and fire reaction : Fire resistance concerns the building element (minutes), fire reaction concerns the material surface (flame spread). A material with excellent fire reaction (Class A) does not necessarily provide fire resistance.
180.Using a fire stop without verifying the rating : Each fire stop system is tested for a specific configuration (pipe type, diameter, wall thickness, barrier type). Using a system not tested for your application is a serious violation.
181.Ignoring the maximum annular space : If the annular space exceeds the tested value, the system may not function. You must use a backing material or a different system.
182.Forgetting to restore the fire stop after an intervention : When you replace a pipe or insulation, you must restore the fire stop immediately. A missing fire stop is a breach in the compartmentation.
183.Installing insulation over a fire damper : Dampers must remain accessible and free of any obstruction. Insulation can prevent the damper from closing.
184.Neglecting the protection of combustible insulation : Polyurethane foam without gypsum protection is a violation of the NBCC, even if it is behind a suspended ceiling.
185.Confusing F, FT, and FH ratings :
F : fire resistance only
FT : fire resistance + smoke tightness
FH : fire resistance + hydraulic shock resistance (for plastic pipes)
189.Applying intumescent paint to a dirty or damp surface : Adhesion is compromised, and the protection may detach in the event of a fire.
190.Using ordinary mineral wool as a fire stop : Mineral wool alone is not a certified fire stop. It can serve as backing material, but the complete system must be tested according to CAN/ULC-S115.
191.Forgetting marking requirements : Every fire stop must be labelled. The absence of a label can result in non-compliance during inspection.

11. Exam Tips

194.Memorize the key standards : CAN/ULC-S101 (fire resistance), CAN/ULC-S115 (fire stops), CAN/ULC-S102 (flame spread), CAN/ULC-S114 (non-combustibility).
195.Know the temperature thresholds : 538 °C for steel, 74 °C for dampers, 90 °C for insulation protection.
196.Understand the difference between compartmentation and smoke containment : The former aims to limit fire spread, the latter to limit smoke migration.
197.Know how to read a fire stop selection table : Exams often present tables with pipe/barrier/rating combinations.
198.Review the NBCC articles : Questions often focus on Articles 3.1.5.12, 3.1.5.14, 3.6.4.2, and 3.6.4.3.
199.Practice the basic calculations : Section factor (A/V), annular space, protection thickness.
200.Remember the typical thicknesses : Gypsum 12.7 mm to protect foam, fire stop sealant 12.7 to 25.4 mm, intumescent paint 0.5 to 5 mm.

12. Summary

Fire resistance (FR) is the ability of an element to withstand fire for a specified duration (45 to 180 minutes), evaluated according to three criteria: stability, integrity, thermal insulation.
Fire stops are certified systems installed in penetrations to restore the FRR of the barrier. They are tested according to CAN/ULC-S115.
The NBCC is the national regulatory reference. Articles 3.1.5.12, 3.1.5.14, 3.6.4.2, and 3.6.4.3 are essential for the heat and frost insulator.
Fire stop materials include sealants (intumescent and endothermic), mortars, boards, pillows, intumescent paints, and collars.
Steel fireproofing aims to keep the temperature below 538 °C. The section factor (A/V) determines the required protection thickness.
Smoke containment is ensured by smoke barriers, dampers, and expansion joints. Smoke causes the majority of fire-related deaths.
Combustible insulation (foams) must be protected by a non-combustible material at least 12.7 mm thick.
When working on piping passing through barriers, the heat and frost insulator must restore the fire stop and never obstruct dampers.
Inspection and documentation are ongoing responsibilities. Every fire stop must be labelled and recorded.

13. Review Questions

214.What is the difference between an F rating and an FT rating?
215.What is the critical temperature threshold for structural steel?
216.Which standard governs fire stop testing for penetrations?
217.Which NBCC article requires the protection of plastic foam insulation?
218.How do you calculate the section factor (A/V)?
219.What is the minimum gypsum thickness required to protect foam insulation?
220.Why must insulation be removed over 300 mm on each side of a fire barrier?
221.What are the three criteria evaluated during a fire resistance test according to CAN/ULC-S101?
222.What is the typical activation temperature of a fire damper?
223.What information must appear on a fire stop label?

This chapter prepares you for the Red Seal exam questions on passive fire protection. Master the standards, calculations, and installation procedures to pass your exam and practice your trade safely.

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free