Chapter VII

Fixtures and Appliances

Red Seal Practice study guide with diagrams.

Plumbing Fixtures and Accessories

Chapter Introduction

This chapter covers all the knowledge required for the Red Seal exam concerning the installation, connection, verification, and troubleshooting of plumbing fixtures and their accessories. You must master not only the operating principles but also the regulatory requirements of the National Plumbing Code of Canada (NPC) and relevant CSA standards. This chapter is structured to follow the exam logic: first classifications and definitions, then installation requirements, load calculations, and finally typical traps.


Classification of Plumbing Fixtures

Regulatory Definition

According to the NPC, a plumbing fixture is any receptacle or fixed device that receives potable water or wastewater and is connected to a drainage system. This definition excludes water treatment equipment and appliances not connected to drainage (e.g., portable dishwashers).

Main Categories

CategoryExamplesInstallation Particularity
Gravity-drainage fixturesSinks, bathtubs, showers, lavatoriesMinimum slope of 2% (¼ in/ft) on the drain
Pressure-flush fixturesPressure-assisted toilets, valve-type urinalsRequire supply pressure ≥ 345 kPa (50 psi)
Fixtures with integral pumpSump stations, garbage disposersElectrical connection required, dedicated venting
Specialized fixturesFountains, therapeutic baths, laboratory sinksSpecific CSA standards (CSA B45.0, CSA B45.5)

Applicable Manufacturing Standards

Every installed fixture must be certified to a recognized CSA standard:

CSA B45.0: General requirements for ceramic plumbing fixtures.
CSA B45.1: Ceramic sinks and basins.
CSA B45.2: Enamelled steel bathtubs.
CSA B45.5: Toilets and urinals (flush performance, water volume ≤ 6.0 L).
CSA B45.10: Fibreglass-reinforced plastic fixtures.
ASME A112.19.2: Vitreous china fixtures (CSA cross-reference).

> Exam Trap: A fixture without a CSA certification mark or equivalent (e.g., UPC, IAPMO) cannot be installed, even if it is functional. The NPC requires independent certification.


General Installation Requirements

Water Supply Connection

Each fixture must be connected to a potable water supply with an accessible individual shut-off valve. Notable exceptions:

Bathtubs (shut-off valve required within 1.5 m).
Showers with thermostatic mixing valves (shut-off valve required).
Toilets (shut-off valve mandatory, typically a ⅜ in angle valve).

The maximum allowable static pressure at the faucet is 550 kPa (80 psi). Beyond this, a pressure-reducing valve (regulator) must be installed on the main supply line.

Drainage Connection

Each fixture must have an individual or shared trap according to the following rules:

One trap may serve two adjacent fixtures if the horizontal distance between the two drains is ≤ 750 mm (30 in).
One trap may not serve more than two fixtures.
Bathtubs and showers must have a 2 in (50 mm) minimum trap.
Kitchen sinks must have a 1½ in (38 mm) minimum trap, but 2 in is recommended if a garbage disposer is installed.

Fixture Venting

Each fixture must be vented in accordance with the NPC, Chapter 2, Part 2.5. Essential rules:

The maximum distance between the trap and the vent (known as the "venting distance") is calculated according to Table 2.5.6.2. of the NPC. For a 1¼ in drain, the maximum distance is 1.2 m; for 1½ in, 1.5 m; for 2 in, 1.8 m; for 3 in, 2.7 m.
Wet venting is permitted for toilets and lavatories in a bathroom, provided the vent drain has a minimum diameter of 2 in.
Relief vents (circuit venting) are required for fixture batteries (≥ 2 fixtures) in commercial installations.

Specific Fixtures: Detailed Requirements

Toilets (WC)

Types and Flush Volumes

TypeFlush VolumeRequired PressureTypical Use
Gravity (tank)4.8 – 6.0 L345 kPa min.Residential
Pressure-assisted3.5 – 4.8 L345 – 550 kPaCommercial, institutional
Vacuum-assisted1.0 – 1.5 L550 kPa min.Airports, hospitals
Composting0 L (waterless)N/ACottages, remote sites

Installation Rules

The clearance in front of the toilet must be ≥ 600 mm (24 in).
The side clearance between the centre of the toilet and a wall or another fixture must be ≥ 375 mm (15 in).
The flange must be secured to the finished floor, with the top of the flange level with the finish.
The wax seal or alternative (rubber ring) must be centred and compressed evenly.
The bowl must be secured with brass or stainless steel bolts, never carbon steel (corrosion).

Frequent Exam Errors

Confusing the 375 mm distance (centre to wall) with the 300 mm distance (centre to wall for a lavatory).
Forgetting that the toilet must be the last fixture connected to the drain (closest to the drainage stack) in a bathroom, to prevent backflow.

Bathtubs and Showers

Bathtubs

The bathtub must be installed with a support if the span exceeds 1.5 m without support.
The integral overflow must be connected to the trap, never directly to the drain.
The bathtub trap must be 2 in (50 mm) minimum, with a 2% slope.
The tub-shower valve assembly must comply with CSA B125.1 (faucets) and ASME A112.18.1.

Showers

The shower base must have a 2 in (50 mm) minimum drain.
The waterproof membrane (liner) must extend at least 50 mm (2 in) above the threshold of the base.
A thermostatic mixing valve is mandatory for showers in healthcare facilities (hospitals, residences) according to the NPC, Article 2.6.3.2. The maximum outlet temperature is 49 °C (120 °F).
The shower floor slope (if a site-built receptor) must be 1:50 toward the drain.

> Exam Trap: A thermostatic mixing valve is not mandatory in a single-family private residence, but it is strongly recommended. Do not confuse it with a mechanical mixing valve (without thermostat) which does not maintain temperature.

Sinks and Lavatories

Kitchen Sinks

The drain must be 1½ in (38 mm) minimum; 2 in if a garbage disposer is installed.
The garbage disposer must be connected to the drain with a 2 in trap and dedicated venting if the distance to the main trap exceeds 1.5 m.
The dishwasher must be connected to the sink drain with a vacuum breaker (backflow preventer) conforming to CSA B64.2, installed above the countertop.
The sink faucet must have a spout with an air gap of at least 25 mm above the rim of the highest receptacle.

Lavatories (Bathroom)

1¼ in (32 mm) minimum drain.
The overflow of the lavatory is integral and must be free of any obstruction.
Sensor faucets (infrared) must conform to CSA B125.1 and have a Class 2 electrical supply (24 V AC or 12 V DC).
Mounting height of the lavatory: top edge between 800 and 850 mm from the finished floor (residential use).

Urinals

1½ in (38 mm) minimum drain, with integral or individual trap.
The flush must be limited to 1.9 L per use (flush-type urinal) or 0 L (waterless urinal).
Waterless urinals use a sealant liquid cartridge; the cartridge must be replaced according to the manufacturer's instructions (typically every 5,000 to 7,000 uses).
The venting of the urinal must be individual or shared with another urinal in the same room.

Therapeutic Baths and Spas

Electrical connection in accordance with the Canadian Electrical Code, Part I (CE Code) (Rule 8-200 for branch circuits).
The drain must be 2 in minimum, with a trap with permanent seal.
The circulation pump must be accessible for maintenance.
A backflow preventer of type RP (reduced pressure) is required on the water supply if the bath is equipped with a recirculation pump.

Load Calculations and Sizing

Fixture Units

The NPC uses the fixture unit (F.U.) system for sizing pipes. Each fixture has a fixed value:

FixtureFixture Units (Supply)Fixture Units (Drainage)
Toilet (6 L tank)2.53
Toilet (pressure-assisted)3.03
Lavatory (bathroom)1.01
Kitchen sink1.52
Bathtub2.02
Shower2.02
Urinal (flush)2.02
Waterless urinal0.51
Dishwasher1.52
Garbage disposer1.01
Laundry (sink + machine)2.03

Sizing Supply Pipes

The sizing method uses Table 2.6.1.2. of the NPC. Steps:

92.Calculate the total fixture units (supply) for all fixtures.
93.Determine the probable flow rate (L/min) using the probability table (simplified Hunter's curve).
94.Choose the pipe diameter based on velocity (≤ 2.4 m/s) and pressure loss (≤ 1 m/100 m).

Calculation Example:

Single-family house: 2 full bathrooms (2 × [WC + lavatory + shower]) + kitchen (sink + dishwasher) + laundry.
Total F.U. = (2.5 + 1 + 2) × 2 + (1.5 + 1.5) + (2 + 1) = 11 + 3 + 3 = 17 F.U.
Probable flow ≈ 30 L/min (according to table).
Minimum main supply pipe diameter: ¾ in (19 mm) copper type M or ¾ in PEX.

Sizing Drains

Table 2.5.7.1. of the NPC gives minimum diameters:

Drain Diameter (in)Maximum Fixture UnitsMinimum Slope
12%
32%
262%
3201%
41601%

> Exam Trap: A 2 in drain can support 6 F.U. at a 2% slope, but only 4 F.U. if the slope is reduced to 1%. The slope affects hydraulic capacity.


Safety Rules and Backflow Protection

Backflow Preventers

According to the NPC, Article 2.6.3.1., any cross-connection between potable water and a source of contamination must be protected. Devices are classified by risk level:

Device TypeCSA StandardTypical UseProtection Level
Air gapSink faucets, dishwashersHigh (air space ≥ 25 mm)
Double check valve assembly (DCVA)CSA B64.5Residential irrigationLow to medium
Reduced pressure principle device (RP)CSA B64.4Boiler supply, therapeutic bathsVery high
Double check valve (DC)CSA B64.5Pollution protection (non-toxic)Medium

Specific Rules

A vacuum breaker must be installed on any exterior faucet (hose bib) with threads (CSA B64.2 standard).
Toilets with tanks have an integral backflow preventer (flush valve), but a pressure-assisted toilet requires an RP if the supply pressure exceeds 550 kPa.
Dishwashers must have a vacuum breaker or an air gap, never a simple check valve.

Installation and Commissioning Procedures

Toilet Installation (Typical Procedure)

116.Check the alignment of the flange: it must be level, at 90° to the finished wall.
117.Install the wax seal on the flange (or the rubber ring).
118.Set the toilet, pressing evenly to compress the seal.
119.Tighten the bolts alternately (cross-pattern), without over-tightening (torque of 5–7 N·m).
120.Connect the water supply with a stainless steel braided flexible hose (not rigid copper).
121.Open the shut-off valve, check for leaks at the seal and the tank.
122.Test the flush: the volume must be ≤ 6.0 L and complete emptying in ≤ 10 seconds.

Shower Commissioning

124.Purge air from the pipes (open the valve in hot position then cold).
125.Check the outlet temperature with a thermometer: ≤ 49 °C for thermostatic mixing valves.
126.Test the pressure: between 345 and 550 kPa.
127.Check the base for watertightness (fill with water to the threshold, observe for 10 minutes).
128.Check the flow rate: ≥ 9.5 L/min for a standard shower, ≥ 7.6 L/min for a low-flow shower.

Traps to Avoid

131.Confusing fixture units: Supply and drainage use different values for the same fixture. Example: a toilet = 2.5 F.U. (supply) but 3 F.U. (drainage).
132.Forgetting venting: A fixture without adequate venting causes siphoning of the water seal. The trap-to-vent distance is often miscalculated.
133.Neglecting the slope: A 1% slope (⅛ in/ft) is acceptable for a 3 in drain, but never for a 1½ in drain (minimum 2%).
134.Installing a vacuum breaker too low: The vacuum breaker must be above the highest overflow point of the fixture. If it is lower, it does not protect.
135.Using carbon steel bolts to secure a toilet: they rust and break.
136.Forgetting the individual shut-off valve: Every fixture must have one, except for very limited exceptions (e.g., bathtub with difficult access).
137.Confusing standards: CSA B45.5 is for toilets, not bathtubs. Always read the label.
138.Not checking pressure: A pressure > 550 kPa without a pressure-reducing valve is a violation of the NPC.
139.Connecting the bathtub overflow to the drain: The overflow must go to the trap, never directly to the main drain.
140.Installing a dishwasher without a vacuum breaker: Backflow of dirty water into the dishwasher is a major health risk.

Summary

Plumbing fixtures are classified by type (gravity, pressure, pump) and must be certified to CSA B45.x standards.
Each fixture requires an individual shut-off valve, a trap (except for exceptions), and venting in accordance with the NPC.
Venting distances and drain diameters are governed by specific tables (NPC 2.5.6.2 and 2.5.7.1).
Fixture units (F.U.) are the basis for sizing: supply (Table 2.6.1.2) and drainage (Table 2.5.7.1).
Backflow protection is mandatory: air gap, check valve, or RP depending on the risk level.
Thermostatic mixing valves are mandatory in healthcare facilities (temperature ≤ 49 °C).
Toilet flush volumes are limited to 6.0 L (residential) and 1.9 L (urinals).
Commissioning procedures include air purging, pressure tests, and temperature verification.

Self-Assessment Questions (Exam-Type)

153.What is the maximum distance between the trap of a lavatory (1¼ in drain) and its vent?
a) 1.2 m
b) 1.5 m
c) 1.8 m
d) 2.7 m

(Answer: a)

159.A garbage disposer is installed on a kitchen sink. What is the minimum drain diameter?
a) 1¼ in
b) 1½ in
c) 2 in
d) 3 in

(Answer: c)

165.What is the maximum allowable pressure at a faucet without a pressure-reducing valve?
a) 345 kPa
b) 450 kPa
c) 550 kPa
d) 700 kPa

(Answer: c)

171.How many fixture units does a waterless urinal have for drainage?
a) 0.5
b) 1
c) 2
d) 3

(Answer: b)

177.Which backflow prevention device is required for a therapeutic bath with a recirculation pump?
a) Air gap
b) Single check valve
c) Reduced pressure principle device (RP)
d) Double check valve

(Answer: c)


Key Normative References

National Plumbing Code of Canada (NPC) 2020: Chapters 2 (installations), 3 (materials), 4 (wastewater).
CSA B45.0 / B45.1 / B45.2 / B45.5 / B45.10: fixture standards.
CSA B125.1: faucets and accessories.
CSA B64.2 / B64.4 / B64.5: backflow prevention devices.
Canadian Electrical Code, Part I (CE Code): Rule 8-200 (branch circuits for fixed appliances).

> Final Advice: On the exam, read each question twice. The most common traps involve fixture units, minimum diameters, and venting distances. Memorize the NPC tables, not isolated values. Good luck with your preparation!