Chapter X

System Protection and Coordination

Red Seal Practice study guide with diagrams.

Protection and Coordination of Systems

Introduction

Protection and coordination of electrical systems form the core of reliability and safety in the distribution network. As a powerline technician, you must understand how protection devices interact to isolate a fault while minimizing the impact on customers. This chapter covers fundamental principles, devices, coordination calculations, and Canadian regulatory requirements.

Fundamental Principles of Protection

Objectives of Protection

Protection of an electrical network aims at three main objectives:

7.Equipment protection: limiting damage caused by fault currents (conductor melting, transformer damage, etc.)
8.Personnel protection: ensuring the safety of workers and the public
9.Continuity of service: minimizing the extent and duration of interruptions

Characteristics of a Fault

A fault is an unwanted path for current. The most common types of faults:

Fault TypeDescriptionRelative Frequency
Single line-to-groundPhase-to-ground contact70-80%
Line-to-lineContact between two phases10-15%
Double line-to-groundTwo phases and ground5-10%
Three-phaseContact between three phases2-5%

The fault current (I_fault) depends on:

The system voltage
The source impedance (upstream network)
The conductor impedance to the fault point
The fault impedance itself (electric arc)

Fault Current Calculation

For a symmetrical three-phase fault:

I_fault = V_phase / Z_total

Where:

V_phase = phase-to-ground voltage (V)
Z_total = total circuit impedance to the fault point (Ω)

Example: For a 25 kV system (phase-to-phase voltage), with a total impedance of 2 Ω:

V_phase = 25,000 V / √3 = 14,434 V
I_fault = 14,434 / 2 = 7,217 A

Protection Devices

Fuses

Fuses and Protection — fuse operation under fault conditions Fuses and Protection — Operation Under Fault Conditions Normal Circuit Source 120 V Fuse Load (Load) I = 5 A Normal current Fault Condition Source 120 V Fuse Short circuit I = 500 A+ Overcurrent (Overcurrent) Result: The fuse protects the circuit 1. The fuse element heats up and melts 2. An electric arc forms briefly 3. The arc is extinguished by the sand or the extinction chamber 4. The circuit is open — no more current Open Canadian interprovincial standards (Red Seal) Normal current Fault current Fuse Fault Sweep = teaching sequence

The fuse is the simplest and most economical protection device. It protects against overcurrents by melting its calibrated element.

Main Characteristics

CharacteristicDescription
Rated current (I_n)Current the fuse can carry continuously
Minimum melting currentMinimum current that melts the element
Interrupting ratingMaximum current the fuse can interrupt
Opening timeTime between fault initiation and opening

Types of Fuses

Expulsion fuses: use gases produced by the arc to blow out the arc. Limited interrupting ratings (up to approximately 8,000 A).
Current-limiting fuses: contain quartz sand that cools the arc. High interrupting ratings (up to 50,000 A+).
Cutout: outdoor mounting with replaceable fuse, used on distribution systems.

Time-Current Curves (TCC)

Time-current curves (TCC) graphically represent the melting time of a fuse as a function of current. These curves are essential for coordination.

Minimum melting curve: minimum time for the fuse to begin melting
Total clearing curve: maximum time for the fuse to completely interrupt the current

Protection Relays

Protection relays detect abnormal conditions and command the opening of circuit breakers. They offer more flexibility than fuses.

Overcurrent Relays

Time overcurrent relay (51): operates with an inverse time delay relative to current
Instantaneous overcurrent relay (50): operates without intentional delay
Ground overcurrent relay (51N/50N): detects ground fault currents

Relay Characteristics

ParameterDescription
Pickup (threshold)Minimum current that activates the relay
Time DialAdjusts the time delay curve
Operating curveTime-current relationship (inverse, very inverse, extremely inverse)

Standardized Curves (IEEE/ANSI)

Inverse (moderately inverse): T = 0.14 / (I/I_p)^0.02 - 1
Very inverse: T = 13.5 / (I/I_p)^1 - 1
Extremely inverse: T = 80 / (I/I_p)^2 - 1

Where T = time (seconds), I = fault current, I_p = pickup current.

Circuit Breakers

The circuit breaker is a mechanical device capable of making, carrying, and interrupting currents under normal and abnormal conditions.

Types of Circuit Breakers

TypeVoltageApplication
Oil circuit breakerMedium voltageDistribution substations
Vacuum circuit breakerMedium voltageModern substations
SF6 circuit breakerHigh voltageTransmission substations
Air blast circuit breakerHigh voltageOlder substations

Interrupting Rating

The interrupting rating is the maximum current the circuit breaker can interrupt without damage. It must be greater than the maximum fault current at the point of installation.

Disconnect Switches and Switches

Disconnect switch: device without load-break capability, used to isolate de-energized equipment
Switch: capable of interrupting rated current, but not fault currents
Load-break switch: combines both functions, with load-break capability

Protection Coordination

Coordination Principles

Coordination consists of selecting and setting protection devices so that only the device closest to the fault operates, leaving the rest of the network in service.

Basic Rule

The upstream protection device must have an operating time greater than the downstream device for the same fault current.

Coordination Margins

Between fuses: minimum margin of 0.25 seconds between the total clearing curve of the downstream fuse and the minimum melting curve of the upstream fuse
Between relays: margin of 0.3 to 0.4 seconds (including circuit breaker opening time)
Between relay and fuse: margin of 0.2 to 0.3 seconds

Coordination Steps

74.Identify possible fault points (beginning of line, end of line, substations)
75.Calculate fault currents at each point
76.Plot TCC curves of all devices on the same graph
77.Verify margins between curves
78.Adjust settings (pickup, time dial) if necessary
79.Verify equipment protection (transformers, conductors)

Fuse-to-Fuse Coordination

For proper coordination between two fuses in series:

The upstream fuse must have a higher rated current than the downstream fuse
The curves must be spaced by at least 0.25 seconds
The ratio of rated currents is generally 1.5 to 2

Relay-to-Relay Coordination

Coordination between relays uses the time dial to create a time offset:

The relay closest to the source has a higher time dial
Each upstream relay adds an additional delay

Transformer Protection

Overload Protection

Distribution transformers are protected against overloads by fuses or relays. Overload capacity depends on ambient temperature and prior loading.

Internal Fault Protection

Buchholz relay (oil-filled transformers): detects gas accumulation
Pressure relay: detects rapid pressure variations
Differential relay: compares primary and secondary currents

Transformer Protection Rules

According to the Canadian Electrical Code, Part I (CE Code) (Rule 26-250), each transformer must be protected against overcurrents. The primary fuse must be calibrated to:

Not melt at the transformer's rated current
Melt in the event of a secondary fault
Protect the transformer against internal faults

Transformer Rated Current Calculation

I_rated = S / (√3 × V)

Where:

S = apparent power (kVA)
V = phase-to-phase voltage (V)

Example: 300 kVA transformer, 25 kV:

I_rated = 300,000 / (√3 × 25,000) = 6.93 A
Recommended fuse: 10 A (approximately 1.5 × I_rated)

Distribution Line Protection

Conductor Protection

Conductors must be protected against fault currents that could damage them. The conductor damage curve (I²t) must be above the clearing curve of the protection device.

Overhead Line Protection

Branch fuses: protect lateral taps
Reclosers: automatically interrupt and reclose the circuit
Sectionalizers: isolate faulted sections

Reclosers

The recloser is an automatic circuit breaker with a reclosing sequence. It distinguishes temporary faults (tree branches on lines, lightning) from permanent faults.

Typical Reclosing Sequence

OperationTimeDescription
1st trip0.1 sFault detection
1st reclose2 sFault test
2nd trip0.1 sIf fault persists
2nd reclose15 sNew test
3rd trip0.1 sIf fault persists
LockoutPermanent fault

Coordination with Branch Fuses

The recloser must be coordinated with branch fuses:

Coordination mode: the fuse melts before the recloser (for permanent faults)
Non-coordination mode: the recloser operates before the fuse (for temporary faults)

Grounding and Lightning Protection

Grounding

Grounding is essential for:

Limiting overvoltages
Ensuring protection operation
Protecting personnel

Types of Grounding

TypeDescriptionApplication
System groundingConnects the neutral to groundSubstations, transformers
Equipment groundingConnects metal enclosuresEquipment
Work groundingProtects workersLive-line work

Surge Arresters

The surge arrester protects equipment against lightning and switching overvoltages.

Characteristics

Maximum continuous operating voltage (MCOV): maximum voltage in continuous service
Residual voltage: terminal voltage during lightning current discharge
Nominal discharge current: 5 kA, 10 kA, 20 kA depending on application

Insulation Coordination

Insulation coordination consists of selecting insulation levels compatible with surge arresters. The arrester protection level must be lower than the equipment withstand level.

Canadian Regulatory Requirements

Canadian Electrical Code, Part I (CE Code)

The Canadian Electrical Code, Part I (CE Code) (current edition) governs electrical installations of distribution systems. The main rules concerning protection:

RuleRequirement
Rule 14-100Protection against overcurrents
Rule 26-250Transformer protection
Rule 14-010Conductor protection
Rule 28-100Motor protection
Rule 10-200Grounding
Rule 10-300Lightning protection

CSA B149.1

CSA B149.1 (Natural Gas and Propane Installation Code) is relevant for gas installations near power lines but does not apply directly to electrical protection.

Relevant CSA Standards

CSA C22.2: standards for electrical equipment
CSA C411: surge arresters
CSA C571: distribution transformers

Work Procedures

Verification of Protection Devices

Before any intervention, verify:

153.The physical condition of fuses and cutouts
154.Relay settings (pickup, time dial)
155.Circuit breaker operation indicators
156.The condition of surge arresters

Fuse Replacement

158.Identify the faulty fuse (visual indicator, testing)
159.Verify absence of voltage (voltage detector)
160.Ground the conductors (grounding sticks)
161.Remove the fuse with the universal hot stick
162.Install the new fuse of the same rating
163.Remove the grounds and verify operation

Relay Setting

165.Calculate fault currents at critical points
166.Select the appropriate curve (inverse, very inverse)
167.Set the pickup at 1.25 × the maximum rated current
168.Set the time dial to ensure coordination
169.Document the settings and verify with an operational test

Practical Calculations

Single-Phase Fault Current Calculation

I_fault_1φ = V_phase / (Z_source + Z_line + Z_fault)

For a phase-to-ground fault with zero fault impedance:

I_fault = V_phase / (Z_source + Z_line)

Voltage Drop Calculation

ΔV = √3 × I × L × (R × cos φ + X × sin φ)

Where:

I = current (A)
L = line length (km)
R = resistance per km (Ω/km)
X = reactance per km (Ω/km)
cos φ = power factor

Complete Coordination Example

Situation: 25 kV distribution line with:

Branch fuse: 15 K (fast curve)
Line head fuse: 40 T (slow curve)
Fault current at the end of the branch: 800 A
Fault current at the beginning of the line: 3,500 A

Verification:

190.For an 800 A fault in the branch:
Melting time of 15 K fuse: 0.05 s
Melting time of 40 T fuse: 0.5 s
Margin: 0.45 s > 0.25 s ✓
194.For a 3,500 A fault at the beginning of the line:
Melting time of 40 T fuse: 0.02 s
The branch fuse is not affected (fault is upstream)

Pitfalls to Avoid

198.Confusing rated current and melting current: the rated current is the continuous current capacity; the melting current is generally 1.5 to 2 times higher.
199.Neglecting the coordination margin: an insufficient margin between two devices can cause simultaneous operation.
200.Forgetting the minimum fault current: coordination must be verified for the minimum fault current (end of line), not just the maximum current.
201.Ignoring ambient temperature: fuses have different characteristics depending on temperature. A fuse operates faster at high temperatures.
202.Using an incorrect fuse rating: always replace a fuse with a fuse of the same rating and type.
203.Confusing minimum and maximum curves: the minimum melting curve and the total clearing curve are not identical.
204.Neglecting ground protection: ground faults are the most frequent and require specific protection.
205.Forgetting to verify the interrupting rating: the device must be able to interrupt the maximum fault current at the point of installation.
206.Not documenting settings: relay settings must be documented and verified periodically.
207.Confusing relay curve types: inverse, very inverse, and extremely inverse curves have different slopes.

Summary

Protection of electrical networks aims to protect equipment, personnel, and ensure continuity of service.
Fuses are simple and economical but offer less flexibility than relays.
Time-current curves (TCC) are the fundamental tool for coordination.
Coordination requires that the upstream device have an operating time greater than the downstream device.
Coordination margins are 0.25 s between fuses and 0.3-0.4 s between relays.
Reclosers distinguish temporary faults from permanent faults.
Grounding and surge arresters protect against overvoltages.
The Canadian Electrical Code, Part I (CE Code) (Rules 14-100 to 14-010, 26-250, 10-200, 10-300) governs distribution installations.
Fault current and coordination calculations must be mastered for the exam.
Personnel safety is paramount: always verify absence of voltage and ground before intervening.

Review Questions

220.What are the three main objectives of electrical network protection?
221.What is the difference between an expulsion fuse and a current-limiting fuse?
222.How do you calculate the rated current of a three-phase transformer?
223.What is the minimum coordination margin between two fuses in series?
224.What is a recloser and how does it work?
225.What are the main rules of the Canadian Electrical Code, Part I (CE Code) concerning protection?
226.Why must coordination be verified for the minimum fault current?
227.What is the difference between a disconnect switch and a switch?
228.How do you choose the rating of a transformer protection fuse?
229.What are the three types of standardized relay curves and their equations?

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free