Chapter IX

Hazardous Locations and Special Installations

Red Seal Practice study guide with diagrams.

Hazardous Locations and Special Installations

Chapter Introduction

This chapter covers the regulatory requirements and technical principles relating to hazardous locations and special installations, as defined by the Canadian Electrical Code, Part I (CE Code), Chapter V and related CSA standards. For the Red Seal exam, you must master area classification, equipment selection, installation methods, distance calculations, and special requirements for systems such as generators, storage batteries, and photovoltaic installations. This chapter prepares you to identify, apply, and justify the applicable rules in a practical context.


Classification of Hazardous Locations

Fundamental Definitions

A hazardous location is a place where dangerous concentrations of flammable gases, vapours, dusts, or fibres may exist. The CE Code, Chapter V, Section 18, divides these locations into zones and divisions according to the probability and duration of the presence of the explosive atmosphere.

Zone 0: Continuous or long-duration presence of flammable gas or vapour (more than 1000 hours per year).
Zone 1: Likely to occur in normal operation (between 10 and 1000 hours per year).
Zone 2: Not likely to occur in normal operation, but possible for short periods (less than 10 hours per year).
Division 1: Equivalent to Zones 0 and 1 combined (probable or continuous presence).
Division 2: Equivalent to Zone 2 (unlikely presence).

The following table summarizes the correspondence between zones and divisions for gases and vapours:

ClassificationPresenceApproximate Annual DurationTypical Example
Zone 0Continuous> 1000 hInterior of a solvent tank
Zone 1Probable10 to 1000 hFuel pumping area
Zone 2Unlikely< 10 hWell-ventilated compressor room
Division 1Continuous or probable> 10 hZone 0 + Zone 1
Division 2Unlikely< 10 hEquivalent to Zone 2

Gas and Dust Groups

Gases and vapours are classified into groups according to their ignition behaviour:

Group I: Firedamp mines (methane).
Group IIA: Propane, acetone, ammonia.
Group IIB: Ethylene, hydrogen sulphide.
Group IIC: Acetylene, hydrogen (the most dangerous).

For dusts, the groups are Group IIIA (flyings), Group IIIB (non-conductive dusts), and Group IIIC (conductive dusts). Equipment selection must account for the specific group: equipment certified for Group IIA is not suitable for Group IIC.

Ignition Temperatures and Temperature Classes

Each gas or dust has an auto-ignition temperature (AIT). Electrical equipment must never have a surface temperature exceeding 80% of the AIT of the gas or dust present. The CE Code defines six temperature classes (T1 to T6):

ClassMaximum Surface Temperature (°C)
T1450
T2300
T3200
T4135
T5100
T685

Example: For hydrogen (AIT ≈ 560 °C), Class T1 is suitable. For carbon disulphide (AIT ≈ 90 °C), only Class T6 is acceptable.


Electrical Equipment for Hazardous Locations

Types of Protection

The CE Code recognizes several types of protection for equipment installed in hazardous areas:

Ex d (explosion-proof enclosure): The enclosure contains an internal explosion and prevents its propagation to the outside. Suitable for Zones 1 and 2.
Ex e (increased safety): Additional measures to prevent arcs, sparks, or abnormal overheating. Suitable for Zones 1 and 2 (under conditions).
Ex i (intrinsic safety): Electrical energy is limited to a level incapable of causing ignition. Suitable for Zones 0, 1, and 2.
Ex p (pressurized enclosure): The enclosure is maintained under positive pressure with an inert gas. Suitable for Zones 1 and 2.
Ex n (protection for Zone 2): Designed specifically for Zone 2, including modes Ex nA (non-sparking), Ex nC (sealed enclosure), Ex nR (restricted breathing).

The following table compares the types of protection:

TypeSymbolApplicable ZonePrinciple
Explosion-proofEx d1, 2Contains the explosion
Increased safetyEx e1, 2Avoids ignition sources
Intrinsic safetyEx i0, 1, 2Limits energy
PressurizationEx p1, 2Prevents gas entry
Zone 2Ex n2Simplified design

Equipment Marking

All certified equipment must bear a marking indicating:

39.The type of protection symbol (Ex d, Ex i, etc.).
40.The gas group (IIA, IIB, IIC).
41.The temperature class (T1 to T6).
42.The name of the certification body (CSA, UL, etc.).

Example of marking: Ex d IIC T6 means explosion-proof, Group IIC, maximum surface temperature 85 °C.

Rule 18-100 and Subsequent Rules

Rule 18-100 requires that all equipment installed in a hazardous location be certified for the intended use. Rules 18-102 to 18-108 deal with specific installations: wiring, fittings, cable glands, seals, etc.

Rule 18-102: Conduits must be threaded with at least 5 full threads engaged.
Rule 18-104: Conduit seals must be sealed within 450 mm of the entrance to an explosion-proof enclosure.
Rule 18-108: Cables must be installed in conduit or be of the armoured type with certified cable glands.

Common trap to avoid: Do not confuse the sealing requirements for Zones 1 and 2. In Zone 2, seals are required only if the enclosure contains contacts capable of producing arcs.


Special Installations: Generators and Motors

Standby and Replacement Generators

Generators installed in buildings must comply with Rule 26-200 of the CE Code. Key requirements include:

Connection: An automatic or manual transfer switch must prevent parallel operation with the distribution system.
Grounding: The generator neutral must be grounded in accordance with Rule 10-200.
Overcurrent protection: Each ungrounded conductor must be protected by a circuit breaker or fuse sized according to Rule 14-100.

Sizing calculation: For a 150 kVA, 600 V three-phase generator, the rated current is:

I = P / (√3 × U) = 150,000 / (1.732 × 600) ≈ 144 A

The circuit breaker must be rated at 150 A or 175 A depending on commercial availability, in accordance with Rule 14-104 (maximum setting of 125% of rated current).

Motors in Hazardous Locations

Motors installed in Zones 1 or 2 must be certified for the location. Explosion-proof motors (Ex d) are common for pumps and fans. Requirements include:

Overload protection: In accordance with Rule 28-300, with a thermal relay set at 125% of full-load current.
Short-circuit protection: Fuses or circuit breakers sized according to Rule 28-200.
Wiring: Conductors must be sized for 125% of full-load current (Rule 28-106).

Example: 25 hp motor, 600 V, full-load current of 24 A. The conductor must be sized for 24 × 1.25 = 30 A. A #10 AWG cable (35 A at 75 °C) is suitable.


Photovoltaic (PV) Installations

Requirements of Rule 64-200

Photovoltaic installations are covered by Section 64 of the CE Code. Key rules include:

Rule 64-200: PV circuit conductors must be sized for 125% of the maximum short-circuit current (Isc) of the module.
Rule 64-204: Inverter output circuit conductors must be sized for 125% of the rated output current.
Rule 64-206: Overcurrent protection devices must be installed on each ungrounded conductor.

Sizing calculation: For a module with Isc = 9.5 A, the sizing current is:

I = 9.5 × 1.25 = 11.875 A

The conductor must be sized for at least 11.875 A, and the circuit breaker for 15 A (standard value).

Grounding of PV Systems

Rule 64-210 requires grounding of module frames and metal supports. The grounding conductor must be sized according to Rule 10-114, based on the rated current of the protected circuit.

Common trap to avoid: PV modules with aluminium frames require contact washers or star washers to ensure a reliable electrical connection, because aluminium naturally oxidizes.


Storage Batteries

Rule 26-500 and Subsequent Rules

Storage battery installations are covered by Rule 26-500. Requirements include:

Ventilation: Battery rooms must be ventilated to prevent hydrogen accumulation (explosive gas). Ventilation must provide at least 4 air changes per hour.
Separation: Batteries must be installed in dedicated rooms or cabinets, with appropriate signage.
Protection: Conductors between batteries and equipment must be protected against overcurrent.

Conductor Sizing

The maximum charging current is used to size conductors. For a 48 V battery bank with a 100 A charger, conductors must be sized for 100 × 1.25 = 125 A. A #1/0 AWG cable (150 A at 75 °C) is suitable.

Rule 26-508: Batteries must be equipped with an accessible and identifiable disconnecting means.


Grounding and Bonding Systems

Rules 10-200 and 10-300

Rule 10-200 requires grounding of all electrical systems of 50 V or more. Rule 10-300 deals with bonding of metal masses.

Ground resistance calculation: The resistance of a grounding electrode must be less than 25 Ω (Rule 10-400). For industrial installations, a resistance of less than 5 Ω is recommended.

Example: A 3 m long, 16 mm diameter electrode driven into soil with a resistivity of 100 Ω·m:

R = ρ / (2πL) × ln(4L / r) = 100 / (2π × 3) × ln(12 / 0.008) ≈ 5.3 Ω

This value is acceptable according to the CE Code.

Bonding in Hazardous Locations

In hazardous locations, Rule 18-116 requires bonding of all metal masses, including conduits, enclosures, and structures. The bonding conductor must be copper, at least 4 mm².


Temporary and Construction Site Installations

Rule 76-100

Temporary installations (construction sites) are covered by Section 76. Requirements include:

Rule 76-100: All circuits must be protected by ground fault circuit interrupters (GFCIs) rated 30 mA or less.
Rule 76-102: Conductors must be of the armoured cable or rigid conduit type, with adequate mechanical protection.
Rule 76-104: Panelboards must be mounted on stable supports, at a minimum height of 1.5 m.

Common trap to avoid: GFCIs for temporary installations must be tested before each use and at least once per week.


Comparative Tables of Requirements

Comparison of Zones and Divisions

CriterionZone 0Zone 1Zone 2Division 1Division 2
PresenceContinuousProbableUnlikelyContinuous/probableUnlikely
Equipment requiredEx i, Ex dEx d, Ex e, Ex iEx n, Ex dEx d, Ex iEx n, Ex d
Conduit sealingYesYesDepending on conditionsYesDepending on conditions
VentilationSpecialNormalNormalSpecialNormal

Conductor Sizing

ApplicationSizing FactorCE Code Rule
Motor circuits125% of full-load current28-106
PV circuits125% of Isc64-200
Battery circuits125% of charging current26-500
Generators125% of rated current26-200
Lighting circuits100% of rated current8-200

Common Traps to Avoid

115.Confusing zones and divisions: Zone 0 has no direct division equivalent. Division 1 includes Zones 0 and 1.
116.Ignoring the temperature class: Equipment certified for Group IIC but with a T3 class is not suitable for a gas with an AIT of 150 °C.
117.Forgetting seals: Conduit seals are mandatory within 450 mm of an explosion-proof enclosure, even if the conduit run is short.
118.Sizing conductors at rated current: The CE Code requires 125% for most motor and generator circuits.
119.Neglecting bonding: In hazardous locations, all metal masses must be bonded, including non-current-carrying conduits.
120.Using uncertified equipment: CSA or equivalent certification is mandatory for all equipment in hazardous locations.
121.Forgetting GFCIs on construction sites: All temporary circuits must be protected by 30 mA GFCIs.
122.Misinterpreting markings: Ex d IIC T6 means explosion-proof, Group IIC, maximum temperature 85 °C. Do not confuse with Ex e (increased safety).

Summary

Hazardous locations are classified into zones (0, 1, 2) and divisions (1, 2) according to the probability of an explosive atmosphere being present.
Equipment must be certified for the gas group, temperature class, and applicable zone.
Types of protection include Ex d, Ex e, Ex i, Ex p, and Ex n, each with specific applications.
Generators must be connected via a transfer switch and protected against overcurrent.
Motors in hazardous locations require overload and short-circuit protection, with conductors sized at 125%.
PV installations require sizing at 125% of short-circuit current and adequate grounding.
Batteries must be ventilated and protected against overcurrent.
Temporary installations require 30 mA GFCIs and mechanically protected conductors.
Conduit sealing, bonding, and grounding are critical requirements in all hazardous locations.

Review Questions

136.What is the difference between Zone 1 and Zone 2 in terms of duration of presence?
137.Can equipment marked Ex d IIB T4 be installed in an area where propane (Group IIA, AIT 470 °C) is present? Justify your answer.
138.Calculate the sizing current for a 50 hp, 600 V motor with a full-load current of 52 A.
139.What are the sealing requirements for a conduit entering an explosion-proof enclosure in Zone 1?
140.Why is bonding essential in hazardous locations?
141.What is the maximum ground resistance according to Rule 10-400?

Answers to Review Questions

144.Zone 1 has a probable presence of 10 to 1000 hours per year; Zone 2 has an unlikely presence, less than 10 hours per year.
145.Yes, because propane is Group IIA (less stringent than IIB) and its AIT of 470 °C corresponds to Class T1 (450 °C), so T4 (135 °C) is more conservative.
146.I = 52 × 1.25 = 65 A. A #6 AWG conductor (75 A at 75 °C) is suitable.
147.The conduit must be sealed within 450 mm of the enclosure, using a certified sealing compound.
148.It prevents potential differences that could cause sparks in the presence of an explosive atmosphere.
149.The maximum resistance is 25 Ω, but a value below 5 Ω is recommended for industrial installations.

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free