Chapter VI

Motors and Motor Control Systems

Red Seal Practice study guide with diagrams.

Motors and Motor Control Systems

Introduction

This chapter covers all the knowledge required for the Red Seal exam concerning electric motors and their control systems. You must master the operating principles, motor types, starting methods, protections, and control circuits in accordance with the Canadian Electrical Code, Part I (CE Code) . This chapter is structured to follow a logical progression: first the physical principles, then motor types, then starting and protection methods, and finally control circuits and troubleshooting.


Fundamental Principles of Motors

The Rotating Magnetic Field

Rotating Magnetic Field — Stator Rotation Rotating Magnetic Field — Stator Rotation A1 B1 C1 A2 B2 C2 Phase A Phase B Phase C Principle Three windings offset by 120° produce a rotating magnetic field. (rotating magnetic field). Synchronous Speed N_s = (120 × f) / P f = frequency (Hz), P = number of poles Ex.: 60 Hz, 4 poles → 1800 rpm Phase Sequence Order A → B → C determines the direction of rotation (clockwise / counter-clockwise). Swapping two phases reverses the direction. Stator: stationary part of the motor Rotor: rotating part Air gap: space between stator and rotor Rotating field vector Stator windings Waveforms Phase A Phase B Phase C 120° 240°

Every alternating current (AC) motor operates on the principle of the rotating magnetic field. When a balanced three-phase system supplies three coils arranged 120° apart, the resulting magnetic field rotates at a speed called the synchronous speed (Ns).

The synchronous speed is calculated using the following formula:

Ns = 120 × f / P

Where:

Ns = synchronous speed in revolutions per minute (RPM)
f = supply frequency in hertz (Hz) — in Canada, 60 Hz
P = number of motor poles (always an even number)

Calculation example: For a 4-pole motor supplied at 60 Hz:

Ns = 120 × 60 / 4 = 1800 RPM

Slip

Slip (s) is the difference between the synchronous speed and the actual rotor speed, expressed as a percentage:

s = (Ns − Nr) / Ns × 100 %

Where Nr is the actual rotor speed.

For a typical induction motor, the slip at full load varies between 2% and 5%. Zero slip is impossible for an induction motor — it is the very principle of its operation. Torque is produced by the speed difference between the rotating field and the rotor.

Torque and Power

Torque (T) and power (P) are related by the following equation:

P (W) = T (N·m) × ω (rad/s)

Where ω = 2π × Nr / 60

For a three-phase motor, the electrical power absorbed is:

P = √3 × V × I × cos φ

Where:

V = line voltage (V)
I = line current (A)
cos φ = power factor

Efficiency (η) is the ratio of mechanical output power to electrical input power:

η = P_output / P_input × 100 %


Types of Motors

Direct Current (DC) Motors

DC motors are classified according to the connection of the field winding relative to the armature:

TypeConnectionMain Characteristic
SeriesField in series with the armatureVery high starting torque, speed varies with load
Shunt (parallel)Field in parallel with the armatureRelatively constant speed
CompoundCombination of series and shuntCompromise between torque and speed regulation

The series motor is used for traction applications (overhead cranes, locomotives) due to its high starting torque. Caution: a series motor must never run at no load — the speed can become dangerously high (runaway).

Three-Phase Induction Motors

This is the most common type of motor in industry. The rotor can be:

Squirrel cage: robust, simple, economical
Wound rotor (slip ring): allows resistors to be inserted into the rotor circuit to limit starting current and increase torque

The squirrel cage motor is the most common. Its main characteristics are:

Starting current: 5 to 8 times the rated current
Starting torque: 1.5 to 2 times the rated torque
Power factor: low at no load (0.1 to 0.2), improves under load (0.7 to 0.9)

Synchronous Motors

The synchronous motor runs at exactly the synchronous speed (zero slip). The rotor is supplied with direct current through slip rings and brushes. Typical applications:

Constant-speed drives
Power factor correction (the synchronous motor can be over-excited to supply reactive power)

Single-Phase Motors

Single-phase motors do not produce a rotating field by themselves — they require a starting method:

TypeStarting MethodTypical Application
Split-phaseAuxiliary winding with centrifugal switchFans, small pumps
Permanent capacitorCapacitor in series with the auxiliary windingCompressors, air conditioners
Capacitor-startElectrolytic capacitor with centrifugal switchCompressors, high-torque equipment
Shaded poleCopper ring on the poleSmall fans, timers
UniversalBrushes, operates on AC and DCPortable power tools

Nameplates and Rated Data

Reading the Nameplate

The motor nameplate provides essential information for installation and troubleshooting. You must know how to interpret each piece of data:

DataMeaningTypical Example
Voltage (V)Rated supply voltage575 V
Current (A)Full-load current12.5 A
Power (HP or kW)Mechanical output power10 HP (7.5 kW)
Speed (RPM)Full-load speed1750 RPM
Service factor (SF)Allowable overload factor1.15
Insulation classMaximum allowable temperatureClass F (155 °C)
Power factor (cos φ)At full load0.85
Efficiency (η)Energy efficiency92%

Service Factor

The service factor (SF) indicates the allowable continuous overload beyond the rated power. A motor with SF = 1.15 can operate continuously at 115% of its rated power without exceeding the maximum temperature of its insulation class.

Insulation Classes

ClassMaximum Temperature (°C)Ambient Temperature + Rise (°C)
A10540 + 65
B13040 + 90
F15540 + 115
H18040 + 140

Motor Protection

Overload Protection

Overload protection protects the motor against prolonged excessive currents that cause heating. It does not act on short circuits — that is the role of overcurrent protection devices (fuses or circuit breakers).

According to the Canadian Electrical Code, Part I, Rule 28-306, the overload protection device must be set at:

No more than 125% of the rated current for motors with a service factor ≥ 1.15
No more than 115% of the rated current for other motors

Example: 10 HP motor, 575 V, rated current 12.5 A, SF = 1.15.

Maximum setting = 12.5 A × 1.25 = 15.6 A → choose a relay set at 15 A.

Short-Circuit Protection

Short-circuit protection (fuses or circuit breakers) protects the conductors and the motor against fault currents. Rule 28-200 of the CE Code specifies the maximum values:

Type of ProtectionPercentage of Rated Current
Time-delay fuses300% (max)
Fast-acting fuses300% (max)
Inverse-time circuit breaker250% (max)
Instantaneous-trip circuit breaker800% (max)

If these values do not allow the motor to start, the CE Code permits higher values under certain conditions (Rule 28-204).

Overload Relays — Trip Classes

Thermal overload relays are classified according to their trip time:

ClassTrip Time at 600% of CurrentApplication
1010 secondsMotors with frequent starting
2020 secondsGeneral purpose
3030 secondsHeavy starts (fans, crushers)

Ground Fault Protection

Rule 28-600 of the CE Code requires ground fault protection for motors over 750 V. For low-voltage motors, this protection is generally integrated into the circuit breaker or provided by a residual current relay.


Starting Methods for Three-Phase Motors

Direct-On-Line (DOL) Starting (Full Voltage)

The motor is connected directly to the supply. The starting current is 5 to 8 times the rated current. This method is acceptable for small motors or when the supply capacity is sufficient.

Star-Delta (Y-Δ) Starting

The motor starts in star (Y), which reduces the voltage across each winding to 58% of the line voltage (1/√3). After a time delay, the connection changes to delta (Δ).

Starting current: reduced to 1/3 of the direct starting current
Starting torque: reduced to 1/3 of the direct starting torque

Important: This method only applies to motors whose six winding terminals are accessible and which are designed to operate in Δ at the supply voltage.

Autotransformer Starting

An autotransformer supplies reduced voltage to the motor during starting. Typical taps are at 50%, 65%, and 80% of the rated voltage.

Starting current: reduced proportionally to the square of the voltage ratio
Starting torque: reduced proportionally to the square of the voltage ratio

Example: With a 65% tap, the starting torque is 0.65² = 0.42 (42%) of the direct starting torque.

Stator Resistance Starting

Resistors are inserted in series with the stator windings during starting, then progressively short-circuited. This method is simple but results in significant energy losses.

Variable Frequency Drive (VFD) Starting

The variable frequency drive (VFD) adjusts both voltage and frequency to control speed and torque. Advantages:

Starting current limited to approximately 150% of the rated current
Precise control of speed and acceleration
Energy savings for variable-load applications

The VFD modifies the V/f relationship to maintain a constant flux in the motor. Constant V/f control is the most common: voltage and frequency vary together to maintain the rated ratio.


Control Circuits

Basic Components

A control circuit typically includes:

ComponentSymbolFunction
ContactorKMMakes or interrupts the power circuit
Control relayCRLogic switching in the control circuit
PushbuttonS1, S2Manual control (NO or NC)
Auxiliary contact13-14, 21-22Status feedback from the contactor
Overload relayOLThermal protection of the motor
TimerKTDelay on energization or de-energization
Disconnect switchQSafety isolation

Start-Stop Circuit

The classic start-stop circuit includes:

111.A start pushbutton (NO) in series with the circuit
112.A stop pushbutton (NC) in series
113.An auxiliary contact of the contactor in parallel with the start pushbutton (sealing or holding contact)

Operating sequence:

115.Press the start pushbutton → the contactor coil is energized
116.The main contact closes → the motor starts
117.The auxiliary contact closes → maintains the coil energized after the pushbutton is released
118.Press the stop pushbutton → the coil is de-energized → the motor stops

Circuit with Two Start Pushbuttons (Two-Location Control)

To control a motor from two locations, the start pushbuttons are connected in parallel and the stop pushbuttons in series.

Circuit with Timing

Timers can be:

ON-delay: the timing begins when the coil is energized
OFF-delay: the timing begins when the coil is de-energized

Typical application: star-delta starting — the timer controls the transition from Y to Δ after a predetermined delay (generally 3 to 10 seconds).

Reversing Circuit

To reverse the direction of rotation of a three-phase motor, two phases are interchanged. The circuit includes two contactors:

Contactor KM1: phases L1-L2-L3 in normal order
Contactor KM2: phases L1-L3-L2 (two phases interchanged)

Mandatory electrical interlocking: The two contactors must never be closed simultaneously — this would create a short circuit between phases. Interlocking is achieved by:

NC auxiliary contacts of each contactor in the other's circuit (electrical interlocking)
Mechanical interlocking on the contactors (optional but recommended)

Canadian Electrical Code (CE Code) Rules — Section 28

Rule 28-106 — Supply Conductors

The supply conductors of a motor must have an ampacity of at least 125% of the motor's rated current.

Example: 12.5 A motor → conductors sized for 12.5 × 1.25 = 15.6 A → choose #14 AWG conductors (20 A at 75 °C) or #12 AWG depending on length and voltage drop.

Rule 28-110 — Overcurrent Protection

Each motor must be protected by an overcurrent protection device conforming to Rules 28-200 to 28-210.

Rule 28-500 — Disconnecting Means

A disconnect switch must be installed within sight of the motor or be lockable in the open position. It must be capable of being locked in the open position to permit safe maintenance.

Rule 28-600 — Ground Fault Protection

Mandatory for motors over 750 V. For low-voltage motors, the protection is generally integrated into the circuit breaker or provided by a residual current relay.

Rule 28-602 — Grounding

The motor frame must be grounded in accordance with Section 10 of the CE Code. The grounding conductor must be sized according to Table 16 of the CE Code.

Rule 26-256 — Control Circuit Protection

Control circuits must be protected against overcurrent. The protection must be installed at the origin of the control circuit.


Troubleshooting and Verification

Pre-Commissioning Checks

151.Insulation resistance: measure with a megohmmeter between each phase and ground, and between phases. The minimum acceptable value is generally 1 MΩ per kilovolt of rated voltage (rule of thumb).
152.Winding continuity: verify with an ohmmeter
153.Connections: verify terminal tightness and wiring conformity
154.Direction of rotation: verify before mechanical coupling

Current Measurements

The current of each phase must be measured during operation. A current imbalance between phases greater than 10% indicates a problem:

Voltage imbalance at the source
Defective winding
Loose connection

Common Problems and Causes

SymptomPossible Cause
Motor does not startNo supply, blown fuse, overload relay tripped, defective contactor
Motor starts slowlyLow voltage, incorrect connection (Y instead of Δ), mechanical overload
Motor overheatsOverload, obstructed ventilation, unbalanced voltage, too frequent starting
Abnormal noiseWorn bearings, misalignment, rotor imbalance
Motor vibratesMisalignment, non-rigid base, unbalanced rotor

Pitfalls to Avoid

164.Confusing rated current and starting current: the starting current is 5 to 8 times the rated current — never size conductors or protection based on starting current.
165.Forgetting the 125% factor for sizing supply conductors (Rule 28-106).
166.Confusing protection percentages: 300% for fuses, 250% for inverse-time circuit breakers, 800% for instantaneous-trip circuit breakers.
167.Neglecting interlocking in reversing circuits — this is a frequent exam question and an absolute safety requirement.
168.Using the synchronous speed formula with the number of pole pairs instead of the number of poles: Ns = 120 × f / P, where P is the total number of poles (not the number of pairs).
169.Forgetting that slip is zero for a synchronous motor and non-zero for an induction motor.
170.Not accounting for the service factor in overload protection calculations.
171.Confusing overload relay trip classes: class 10, 20, 30 — the number indicates the trip time at 600% of rated current.
172.Forgetting that star-delta starting reduces torque to 1/3 — this method is not suitable for loads requiring high starting torque.
173.Not checking insulation resistance before commissioning — this is a mandatory step for safety and reliability.

Summary

Synchronous speed is calculated by Ns = 120 × f / P and depends on frequency and the number of poles.
Slip is the difference between synchronous speed and actual speed — it is essential to the operation of induction motors.
Three-phase induction motors are the most common; their starting current is 5 to 8 times the rated current.
The nameplate provides all necessary data: voltage, current, power, service factor, insulation class.
Overload protection (thermal relay) protects against heating; short-circuit protection (fuses, circuit breakers) protects against faults.
Reduced-voltage starting methods (Y-Δ, autotransformer, resistors, VFD) reduce starting current at the cost of reduced torque.
The VFD offers the most complete control: limited starting current, speed control, and energy savings.
Control circuits include contactors, relays, pushbuttons, timers, and interlocks.
The CE Code, Section 28 imposes specific rules: conductors at 125% of rated current, overcurrent protection according to defined percentages, mandatory disconnect switch.
Systematic troubleshooting begins by checking the supply, then the protection, then the motor itself.

Review Questions

188.Calculate the synchronous speed of a 6-pole motor supplied at 60 Hz.
189.A 575 V, 20 HP motor has a rated current of 24 A and SF = 1.15. What is the maximum overload relay setting?
190.What are the maximum short-circuit protection values for a motor protected by time-delay fuses?
191.Why is interlocking mandatory in a reversing circuit?
192.What is the effect of star-delta starting on starting current and torque?
193.A 4-pole induction motor runs at 1740 RPM. What is its slip as a percentage?
194.What are the four insulation classes and their maximum temperatures?
195.What is the difference between a class 10 and a class 30 overload relay?
196.What are the advantages of a variable frequency drive compared to direct-on-line starting?
197.Which CE Code rule specifies the sizing of motor supply conductors?

Normative References

Canadian Electrical Code, Part I — Sections 26 (installation), 28 (motors)
CSA C22.1 — Canadian Electrical Code (reference standard)
CSA C22.2 No. 14 — Industrial control equipment
CSA C22.2 No. 100 — Electric motors
CSA B149.1 — Natural gas and propane installation code (for applications with motors in classified areas)

This chapter covers the essential knowledge for the Red Seal exam in industrial electricity. Mastery of the formulas, CE Code rules, and operating principles is essential. Practice with varied calculations and control circuit diagrams to consolidate your understanding.

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free