Conductors, Cables, and Raceways
Red Seal Practice study guide with diagrams.
Conductors, Cables, and Cable Trays
Chapter Introduction
This chapter covers one of the most heavily tested areas on the Red Seal exam for industrial electricians: the selection, installation, and protection of conductors, cables, and cable trays. You must master the rules of the Canadian Electrical Code, Part I (CE Code) , particularly Chapters 4 (conductors), 6 (cables), and 12 (cable trays). The exam assesses your ability to apply these rules in real industrial contexts: high ambient temperatures, conductor grouping, voltage drop, and selection of installation methods.
Conductors: Types, Designations, and Applications
Conductor Classification
Conductors are classified according to their material, insulation, and temperature rating. Copper and aluminum are the two materials used in industry.
| Property | Copper | Aluminum |
|---|---|---|
| Relative conductivity | 100% | 61% |
| Density | 8.89 g/cm³ | 2.71 g/cm³ |
| Tensile strength | High | Lower |
| Cost | High | Lower |
| Typical use | Circuits ≤ 500 kcmil | Circuits ≥ 1/0 AWG |
Rule 4-000: The CE Code requires conductors to be copper or aluminum unless otherwise specified. In industry, aluminum is common for large sizes (motor feeders, switchgear busbars) due to its lower cost, but it requires specific connectors (anti-oxidation).
Conductor Designations (Insulation Types)
Conductors are identified by a letter code. You must know the following types for the exam:
| Type | Insulation | Max Temperature | Typical Use |
|---|---|---|---|
| **RW90** | Cross-linked polyethylene (XLPE) | 90°C dry/wet | General, industrial |
| **TW** | Polyvinyl chloride (PVC) | 60°C dry/wet | Residential, light |
| **THW** | PVC | 75°C dry, 60°C wet | General |
| **THHN** | Nylon/PVC | 90°C dry, 75°C wet | Conduits, raceways |
| **XHHW** | XLPE | 90°C dry, 75°C wet | Industrial, wet |
| **ACWU** | Aluminum armour, sheath | 90°C | Buried, wet |
| **TECK90** | PVC sheath, steel armour | 90°C | Industrial, wet |
Exam Trap: Type THHN is rated 90°C dry but only 75°C in wet locations. If you are calculating ampacity for an outdoor conduit, you must use 75°C, even if the conductor is marked 90°C.
Temperature Rating and Ampacity
The ampacity (current-carrying capacity) of a conductor depends on:
Rule 4-004: The operating temperature of the insulation must not exceed its rated value. The CE Code tables (D1 to D5) provide base ampacities.
Temperature Correction Factor: For each deviation in ambient temperature from the reference (30°C for most tables), apply a correction factor. For example, for an RW90 conductor at 40°C ambient, the factor is 0.91 (Table 5A of the CE Code).
Calculation Formula:
Corrected ampacity = Base ampacity × Temperature factor × Grouping factor
Example: Three RW90 #2 AWG copper conductors in a conduit at 45°C ambient.
Voltage Drop
Principles and Requirements
Voltage drop is the reduction in voltage between the source and the load, caused by the resistance and reactance of the conductors. It affects the operation of motors, lighting, and electronic equipment.
Rule 8-200: The voltage drop between the point of connection and the point of utilization must not exceed:
Calculation Formulas:
For a single-phase circuit:
ΔV = (2 × L × I × R) / 1000
For a three-phase circuit:
ΔV = (√3 × L × I × R) / 1000
Where:
Percentage Voltage Drop:
%ΔV = (ΔV / V_nominal) × 100
Example: Three-phase motor drawing 50 A at 208 V, supplied by a #6 AWG copper cable (R = 0.51 Ω/km) over 60 m.
ΔV = (√3 × 60 × 50 × 0.51) / 1000 = 2.65 V
%ΔV = (2.65 / 208) × 100 = 1.27% — acceptable (≤ 3%)
Exam Tip: For long runs (> 100 m), always check voltage drop BEFORE finalizing the conductor size. Table D3 of the CE Code provides maximum lengths for various conductor sizes and currents.
Industrial Cables
Armoured and Sheathed Cables
Industrial cables are assemblies of insulated conductors with a protective sheath and sometimes armour. The following types are essential:
| Type | Armour | Sheath | Use |
|---|---|---|---|
| **TECK90** | Helical steel wire | PVC | Industrial, wet, buried |
| **ACWU** | Corrugated aluminum | PVC | Buried, outdoor |
| **AC90** | Aluminum | None (inner sheath) | Dry, indoor |
| **NMWU** | None | PVC | Buried, wet |
| **SOW/SJOOW** | None | Rubber/thermoplastic | Flexible, portable tools |
Rule 12-600: TECK90 and ACWU cables may be installed:
Medium-Voltage Cables (5 kV to 46 kV)
In industry, medium-voltage (MV) cables supply large motors, transformers, and internal distribution networks. Common types include:
Rule 12-012: MV cables must be installed in dedicated cable trays or conduits, with adequate separation from control circuits (see Rule 12-2200 for minimum distances).
MV Cable Terminations: Terminations must be made with approved accessories (termination cones, stress cones) to control the electric field. Incorrect stripping or inadequate shield spacing causes partial discharge and failures.
Control and Instrumentation Cables
Control cables (18 AWG to 10 AWG) and instrumentation cables (thermocouples, RTDs, 4-20 mA signals) have specific requirements:
Rule 12-2200: Minimum distance of 300 mm between control/instrumentation cables and power cables in cable trays, unless a physical barrier (partition) is installed.
Cable Trays
Types and Definitions
Cable trays are continuous support systems for cables. The main types are:
| Type | Description | Typical Use |
|---|---|---|
| **Ladder cable tray** | Two longitudinal rails connected by rungs | Large cables, MV |
| **Solid-bottom cable tray** | Perforated or solid plate | Control cables, small cables |
| **Trough** | U-shaped profile | Control cables |
| **Wire mesh cable tray** | Welded metal grid | Light cables, control |
Rule 12-2300: Cable trays must be supported at maximum intervals of 1.5 m for ladder types and 1.2 m for solid-bottom types, unless otherwise specified by the manufacturer.
Cable Tray Fill
Fill is the percentage of the cable tray cross-sectional area occupied by cables. The limits are:
| Tray Type | Power Cables (all same size) | Control Cables | Mixed |
|---|---|---|---|
| Ladder cable tray | 50% of area | 50% of area | Calculate per Table 12-2300 |
| Solid bottom | 40% of area | 40% of area | 40% |
Rule 12-2302: Fill must not exceed 50% for ladder cable trays. For solid-bottom trays, the limit is 40%. These limits ensure adequate heat dissipation.
Fill Calculation:
Area occupied by cables = Σ (π × d² / 4) for each cable
Percentage fill = (Occupied area / Tray area) × 100
Example: Solid-bottom cable tray 300 mm × 100 mm (area = 30,000 mm²). Cables: 5 × TECK90 3C #4 AWG (outer diameter 28 mm).
Area per cable = π × 28² / 4 = 615.8 mm²
Total area = 5 × 615.8 = 3,079 mm²
Fill = (3,079 / 30,000) × 100 = 10.3% — acceptable
Installation and Support
Rule 12-2310: Cables in cable trays must be:
Bending Radius: The minimum bending radius for TECK90 cables is 7 × the outer diameter (Rule 12-610). For MV cables, the radius can be up to 12 × the diameter.
Exam Trap: Cables in cable trays must not be twisted or crossed. Each cable must be installed parallel to the others, without interlacing.
Conduits and Tubing
Conduit Types
| Type | Abbreviation | Use |
|---|---|---|
| Rigid metal conduit | RMC (GRC) | Heavy industrial, outdoor |
| Rigid aluminum metal conduit | RMC-Al | Corrosion, reduced weight |
| Flexible metal conduit | FMC | Connections, vibration |
| Liquid-tight flexible metal conduit | LFMC | Wet, outdoor |
| Rigid PVC conduit | PVC | Buried, corrosion |
| Electrical metallic tubing | EMT | Indoor, dry |
| Electrical non-metallic tubing | ENT | Indoor, embedded |
Rule 12-1000: The choice of conduit depends on the environment (wet, corrosive, risk of mechanical damage) and the installation method.
Conduit Fill
Conduit fill is limited to allow installation and heat dissipation. The limits are:
| Number of Conductors | Maximum Fill |
|---|---|
| 1 | 53% |
| 2 | 31% |
| 3 or more | 40% |
Rule 12-1014: Table 12-1014 of the CE Code provides conduit dimensions based on the number and size of conductors. You must be able to determine the minimum conduit size.
Calculation Method:
Example: 4 RW90 #2 AWG conductors (area per conductor = 92.3 mm²) in RMC conduit.
Total area = 4 × 92.3 = 369.2 mm²
Required area = 369.2 / 0.40 = 923 mm²
RMC conduit of 27 mm (internal area = 1,013 mm²) — acceptable
Maximum Length and Pulling
Rule 12-1010: The maximum length of a conduit between two pull boxes is 30 m, unless intermediate pull boxes are installed. Each 90° bend reduces the maximum length by 6 m.
Calculation: Equivalent length = Actual length + (Number of bends × 6 m)
The equivalent length must not exceed 30 m.
Example: Conduit of 20 m with 2 × 90° bends.
Equivalent length = 20 + (2 × 6) = 32 m — exceeds 30 m, a pull box must be added.
Grouping and Derating Rules
Grouping Factor
When more than 3 current-carrying conductors are installed in the same conduit or cable tray, the ampacity must be reduced. The factors are:
| Number of Conductors | Derating Factor |
|---|---|
| 4 to 6 | 0.80 |
| 7 to 9 | 0.70 |
| 10 to 24 | 0.70 |
| 25 to 42 | 0.60 |
| 43 and more | 0.50 |
Rule 4-008: These factors apply to current-carrying conductors. Grounding and bonding conductors are not counted.
Exam Trap: In a three-phase circuit with a neutral, the neutral is considered current-carrying if the load is unbalanced or if the loads are non-linear (harmonics). For balanced three-phase loads (motors), the neutral is not counted.
Neutral Conductors and Harmonics
Rule 4-024: The neutral must be sized for the maximum unbalanced current. For non-linear loads (variable frequency drives, switching power supplies), the neutral can carry more current than the phase conductors due to third-order harmonics.
Requirement: For circuits with non-linear loads > 50% of the phase current, the neutral must be at least the same size as the phase conductors.
Grounding and Bonding
Grounding Conductors
Rule 10-200: The grounding conductor must be:
| Phase Conductor Size (Copper) | Minimum Grounding Conductor Size (Copper) |
|---|---|
| ≤ 2 AWG | 8 AWG |
| 1 AWG to 1/0 | 6 AWG |
| 2/0 to 3/0 | 4 AWG |
| 4/0 to 300 kcmil | 2 AWG |
| 350 to 500 kcmil | 1/0 AWG |
Grounding of Cable Trays
Rule 10-402: Sections of metallic cable trays must be bonded together and grounded. Continuity must be ensured by bonding at joints and fittings.
Requirement: Each section of cable tray must be connected to the grounding conductor at maximum intervals of 30 m.
Pitfalls to Avoid
Summary
Key Formulas to Memorize:
Self-Assessment Questions
This chapter prepares you for Red Seal questions on conductors, cables, and cable trays. Review the CE Code tables (D1, D3, 5A, 6A, 16) and practice the calculations until they become automatic. Good luck with your preparation!
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free