Chapter VI

Control Valves and Final Control Elements

Red Seal Practice study guide with diagrams.

Control Valves and Final Control Elements

Control Valves — valve stem travel and flow characteristics Control Valves — Valve Stem Travel and Flow Characteristics Control Valve (cross-section) Inlet Outlet Actuator Stem travel 0–100% Flow Characteristics 100% 50% 0% 0% 50% 100% Stem Travel (%) Flow (%) Linear Equal % Quick opening Key Points (Red Seal) • Linear: flow proportional to travel • Equal %: same % change per unit of travel — good for process control • Quick opening: large flow at low travel • Selection depends on application and pressure drop HVAC — Control Systems (Red Seal) Terminology • Valve stem • Seat / Plug • Actuator • Travel — total displacement • Flow characteristic Inspector / Journeyman — Interprovincial Exam

Introduction

Control valves are the most common final control element in an industrial control loop. They convert the controller's command signal (pneumatic, electronic, or digital) into mechanical movement that changes the process fluid flow rate. For the instrumentation and control journeyperson, mastering control valves is essential: selection, sizing, installation, calibration, and diagnostics. This chapter covers all the knowledge required for the Red Seal exam, including applicable Canadian standards and sizing calculations.


1. Role and Classification of Control Valves

1.1 Function in the Control Loop

The control valve is the final control element. It receives a standardized signal (3-15 psi, 4-20 mA, or digital protocol such as HART, Foundation Fieldbus) and adjusts the flow area to maintain the process variable at setpoint. The relationship between the input signal and the resulting flow depends on the valve's flow characteristic.

1.2 Classification by Action

Normally closed (NC) valve: closes upon loss of signal (air or current). Used for safety (fail-closed).
Normally open (NO) valve: opens upon loss of signal (fail-open). Used for cooling, purging, etc.
Direct acting: increasing signal opens the valve.
Reverse acting: increasing signal closes the valve.

The fail-open/fail-closed choice is dictated by risk analysis (HAZOP) and safety requirements. The examiner will verify that you understand the logic: a loss of air must place the process in the safest state.

1.3 Valve Types by Movement

TypeMovementTypical ApplicationsAdvantagesDisadvantages
**Globe**Linear (stem rises/lowers)Flow, pressure, level controlGood precision, modifiable characteristicsHigh pressure drop
**Butterfly**Rotary (quarter turn)Large diameters, clean fluidsCompact, lightweight, economicalNon-linear characteristic, high torque
**Ball**Rotary (quarter turn)On/off service, fluids with particulatesExcellent shutoff, high flow capacityLess precise for fine regulation
**Eccentric plug**RotaryAbrasive fluids, slurriesLow friction, good shutoffLimited travel
**High-performance butterfly**RotarySteam, gas, clean liquidsLow pressure drop, good control rangeRequires a positioner

2. Inherent Flow Characteristics

The inherent characteristic is the relationship between percent opening (travel) and flow, at constant pressure drop (ΔP). Three main characteristics:

Linear: flow is proportional to travel. For processes where the pressure drop across the valve remains constant (e.g., level control).
Equal percentage: flow increases exponentially with travel. Each increment of travel produces the same percentage increase in flow. This is the most commonly used characteristic for flow and pressure control, as it compensates for variations in ΔP.
Quick opening: maximum flow is achieved with minimal travel (10-20%). Used for on/off valves and safety relief valves.

2.1 Relationship Between Inherent and Installed Characteristics

The installed characteristic accounts for the actual pressure drop in the system (piping, heat exchangers, etc.). A valve with a linear characteristic can behave like a quick-opening valve if the pressure drop in the piping is high. The examiner may ask you to justify choosing an equal-percentage characteristic for a process where the differential pressure varies significantly with flow.

2.2 Flow Coefficient Cv

Cv is the flow of water in US gallons per minute (GPM) that passes through the valve with a pressure drop of 1 psi. It is the fundamental sizing parameter.

Sizing Formulas (Liquids):

For liquids (water and similar fluids):

Cv = Q × √(SG / ΔP)

Where:

Q = flow rate in GPM
SG = specific gravity of the fluid (dimensionless)
ΔP = pressure drop across the valve in psi

Worked Example:

Required flow: 150 GPM, SG = 0.85, available ΔP = 12 psi.

Cv = 150 × √(0.85 / 12) = 150 × √(0.0708) = 150 × 0.266 = 39.9

You must select a valve with a rated Cv ≥ 39.9, ideally with a 20-30% margin (Cv ≈ 50). An oversized valve (Cv too large) results in poor control resolution; an undersized valve cannot achieve the required maximum flow.

Formula for Gases (ISA-75.01.01 standard):

Cv = Q / (1360 × √(ΔP × P1 / (SG_gas × T × Z)))

Where:

Q = flow rate in SCFH (standard cubic feet per hour)
P1 = upstream absolute pressure (psia)
T = absolute temperature in °R (Rankine = °F + 460)
Z = compressibility factor (≈ 1 for ideal gases)
SG_gas = specific gravity of the gas relative to air (air = 1.0)

Choked Flow Condition: when the fluid velocity reaches the speed of sound within the valve, flow no longer increases even if ΔP increases. For gases, critical flow is reached when P2/P1 ≤ 0.55 (approximately). The formula above is only valid for non-choked flow.


3. Mechanical Components of a Control Valve

3.1 Body and Bonnet

Body: cast iron, carbon steel, stainless steel (316 SS), special alloys (Hastelloy, Monel) depending on corrosion and temperature.
Bonnet: standard, extended (for extreme temperatures), bellows seal (for enhanced sealing), packed gland.

3.2 Internal Trim

The trim includes the seat, plug, and cage. Common materials: 316 stainless steel, stellite (for wear resistance), tungsten carbide (for abrasive fluids).

Single-seated plug: good shutoff, but high unbalanced hydraulic force.
Balanced plug (perforated cage): reduces the force required by the actuator, but increases internal leakage.
Double-seated: hydraulically balanced, but higher leakage (not suitable for tight shutoff).

3.3 Packing and Gland

The packing gland provides the seal between the stem and the bonnet. Packing materials can be PTFE (Teflon), graphite, or a combination. Overtightening increases friction and can cause stick-slip: the valve no longer responds linearly to the signal.

3.4 Actuators

TypePower SourceCharacteristicsApplications
**Diaphragm pneumatic**Air 3-15 psi or 20-100 kPaSimple, reliable, economicalThe vast majority of valves
**Piston pneumatic**Air 30-100 psiHigh force, long strokeLarge diameter valves
**Electric**Motor + gearboxSlow, precise, no air requiredRemote sites, safety valves
**Hydraulic**Oil under pressureVery high forceGiant valves, critical processes
**Electrohydraulic**Pump + accumulatorFast, high forceSafety applications

3.5 Positioner

The positioner compares the command signal (4-20 mA or 3-15 psi) to the actual stem position (feedback via cam or sensor) and adjusts the air pressure to the actuator to eliminate the error. It improves linearity, response, and accuracy. Modern positioners are smart (HART, Foundation Fieldbus) and enable remote diagnostics (friction, leakage, total travel).


4. Calculations and Selection: Rules of Thumb

4.1 Sizing Rule (Liquids)

To avoid sizing errors:

67.Calculate the required Cv at maximum flow.
68.Add a 20-30% margin (slight oversizing).
69.Verify that the Cv calculated at minimum flow (often 20% of maximum flow) remains above the valve's minimum Cv (typically 10% of rated Cv).
70.Check the rangeability: the ratio between maximum and minimum controllable flow. A typical globe valve has a rangeability of 50:1; a butterfly valve, 20:1.

4.2 Complete Example (Liquid)

Data:

Maximum flow: 300 GPM
Minimum flow: 60 GPM
SG = 1.0 (water)
Available ΔP: 25 psi

Calculation:

Cv_max = 300 × √(1.0 / 25) = 300 × 0.2 = 60

Cv_min = 60 × √(1.0 / 25) = 60 × 0.2 = 12

Selection: valve with rated Cv = 80 (33% margin). Rangeability: 80 / 8 = 10:1 (minimum controllable Cv ≈ 8). The required Cv_min (12) is greater than 8: the valve can control the minimum flow. If the required Cv_min were below the valve's minimum Cv, a smaller valve or a different characteristic would be needed.

4.3 Cavitation Check

Cavitation occurs when the local pressure drops below the vapor pressure of the liquid, forming bubbles that implode. It causes noise, vibration, and erosion.

Cavitation Index (Kc):

Kc = (P1 - Pv) / (P1 - P2)

Where:

P1 = upstream absolute pressure
P2 = downstream absolute pressure
Pv = vapor pressure of the liquid at service temperature

If Kc < 1.4, there is a risk of cavitation. Solutions: anti-cavitation cage valve, reducing ΔP in multiple stages, or increasing downstream pressure.

4.4 Aerodynamic Noise Check

For gases and steam, valve-generated noise can exceed safety limits (85 dBA). Multi-stage cage valves or valves with integral silencers reduce noise. The ISA S75.17 standard provides the predictive noise calculation method.


5. Installation and Mounting

5.1 Installation Requirements

The valve must be installed with the flow direction indicated by the arrow on the body.
Provide union connections on each side for maintenance.
The valve must be accessible for the actuator and positioner.
Avoid mechanical stress on the body (pipe alignment).
For cryogenic valves, provide an extension bonnet to protect the actuator from cold temperatures.

5.2 Bypass and Manual Override Valve

A bypass (manual valve in parallel) allows the process to remain in service during control valve maintenance. It is mandatory for critical continuous processes. The bypass must be sized for at least 70% of maximum flow.

5.3 Filters and Separators

An air filter regulator must be installed upstream of the positioner to ensure clean, dry instrument air supply (ISA S7.3 standard: instrument air quality). Typical supply pressure is 20-30 psi (140-210 kPa) for a diaphragm actuator, and up to 100 psi for a piston actuator.


6. Calibration and Adjustment

6.1 Positioner Calibration Procedure

107.Mechanical check: ensure the valve stem is free, and the packing gland is properly tightened (neither too tight nor too loose).
108.Connection: connect a calibrated air source (precision regulator) and a reference pressure gauge to the command signal.
109.Zero adjustment: apply the minimum signal (4 mA or 3 psi) and adjust the positioner zero so the valve is at the minimum position (0%).
110.Span adjustment: apply the maximum signal (20 mA or 15 psi) and adjust the span so the valve is at 100%.
111.Linearity check: apply intermediate points (25, 50, 75%) and verify the actual position. The maximum allowable error is typically ±1% of travel.
112.Repeatability test: perform three complete cycles and verify that the position is identical for each point.

6.2 Stroke Adjustment

The valve stroke is the distance between the closed position and the open position. It is indicated on the nameplate (e.g., 1 inch, 2 inches). Adjustment is made via the actuator's mechanical stops. An incorrect stroke causes a valve that either does not close fully or forces against the stop.

6.3 Seat Leak Test

The ISA S75.19 standard classifies internal leakage into six classes (I to VI). Class IV (maximum leakage of 0.01% of rated Cv) is the most common for standard control valves. Class VI (virtually zero leakage) is required for isolation and safety valves.


7. Canadian Standards and Applicable Codes

7.1 Canadian Electrical Code (CE Code)

The Canadian Electrical Code, Part I (C22.1-21) applies to electrical installations, including electric actuators and motorized valves.

Rule 18-100: requirements for hazardous locations (area classification).
Rule 18-152: wiring of instruments in classified areas.
Rule 8-200: grounding and bonding of electrical equipment.

For valves with electric actuators in classified areas, the motor must be certified for the appropriate class and division (or zone). Cables must pass through sealed conduits in accordance with Rule 18-152.

7.2 CSA B149.1 (Natural Gas and Propane Code)

CSA B149.1 applies to natural gas and propane installations. For gas control valves:

Article 6.4: requirements for manual shut-off valves.
Article 6.22: requirements for pressure regulators.
Gas control valves must be CSA certified and installed in accordance with ventilation and clearance requirements.

7.3 CSA B51 (Pressure Equipment Code)

CSA B51 applies to boilers, pressure vessels, and pressure piping. Control valves installed on pressure equipment must meet material and design requirements. Safety relief valves are covered by this standard.

7.4 Other Relevant Standards

ISA-75.01.01: control valve sizing.
ISA-75.02: valve testing procedures.
ISA-75.19: leakage tests.
ASME B16.34: flanged, welded, and threaded valves (pressure-temperature ratings).
ASME B31.1 / B31.3: pressure piping (installation requirements).

8. Diagnostics and Troubleshooting

8.1 Common Symptoms and Causes

SymptomProbable CauseCorrective Action
Valve does not respond to signalLoss of air, misadjusted positioner, stuck stemCheck supply, recalibrate, clean
Valve vibrates or oscillatesGain too high, poorly adjusted positioner, ΔP too lowReduce gain, adjust positioner
Internal leakage (valve closed)Damaged seat, worn trim, distorted bodyReplace trim, reface seat
Excessive noiseCavitation, choked flow, excessive velocityReduce ΔP, install silencer
Slow strokeHigh friction, insufficient air, weak springLubricate, increase pressure, replace spring
High hysteresisPacking friction, mechanical playReplace packing, adjust linkages

8.2 Loop Response Test

The step response test involves applying an abrupt setpoint change and measuring the response time and overshoot. Overshoot greater than 20% indicates excessive gain or an overly aggressive positioner. Response time that is too long indicates excessive friction or an undersized actuator.

8.3 Smart Positioner Diagnostics

Smart positioners (e.g., Fisher DVC6000, Siemens SIPART PS2) provide real-time diagnostics:

Valve signature: graph of position versus signal, revealing friction, hysteresis, and linearity.
Partial stroke test: verifies safety valve functionality without interrupting the process.
Cycle counter: number of openings/closures, useful for predictive maintenance.

9. Safety Valves and Relief Valves

9.1 Distinction Between Control Valves and Relief Valves

Relief valve: opens automatically to relieve overpressure and protects equipment. It is not used for regulation.
Safety valve: opens rapidly (pop action) to protect personnel and equipment in case of extreme overpressure.
Safety shutoff valve: opens or closes on command from a safety system (SIS).

9.2 Relief Valve Installation Requirements

The relief valve must be installed directly on the protected equipment, with no isolation valve between the equipment and the relief valve (except as permitted by code).
The discharge piping must be sized to prevent back pressure.
The relief valve must be accessible for inspection and testing (typically annual).
The set pressure must comply with design calculations (CSA B51).

9.3 Functional Testing of Safety Valves (SIS)

Safety valves in a Safety Instrumented System (SIS) must be tested periodically in accordance with IEC 61511. The test verifies closing time (typically < 2 seconds), tightness, and full stroke. The partial stroke test (PST) verifies functionality without shutting down the process.


10. Practical Considerations for the Exam

10.1 Units and Conversions

The Red Seal exam uses the imperial system for Cv calculations (GPM, psi) and the metric system for dimensions (mm, kPa). You must be proficient with conversions:

1 psi = 6.895 kPa
1 GPM = 3.785 L/min
1 inch = 25.4 mm
1 bar = 100 kPa = 14.5 psi

10.2 Reading the Nameplate

A valve nameplate indicates: rated Cv, maximum working pressure rating, maximum temperature, body and trim material, stroke, and serial number. The examiner may ask you to identify the rated Cv or maximum pressure from a nameplate.

10.3 P&ID Diagrams

On a P&ID (Piping and Instrumentation Diagram), the control valve is represented by a specific symbol. The letters identify the function:

FCV: Flow Control Valve
PCV: Pressure Control Valve
LCV: Level Control Valve
TCV: Temperature Control Valve

Fail-open (FO) and fail-closed (FC) symbols are indicated by an arrow or specific symbol on the P&ID.


Pitfalls to Avoid

181.Confusing Cv and Kv: Cv uses GPM and psi; Kv uses m³/h and bar. The relationship is: Cv = 1.17 × Kv. Never mix units in a calculation.
182.Forgetting specific gravity (SG): for a liquid other than water, the Cv must be multiplied by √SG. Forgetting SG results in a 10-30% sizing error.
183.Neglecting choked flow conditions: for gases, if P2/P1 < 0.55, the flow is choked and the standard formula no longer applies. Use the critical flow formula.
184.Choosing a linear characteristic for a process with variable ΔP: the equal-percentage characteristic is almost always the right choice for industrial processes.
185.Ignoring rangeability: a valve with a rated Cv of 100 cannot accurately control a flow of 2 GPM. Always check the minimum controllable flow.
186.Confusing fail-open and fail-closed: loss of signal must place the valve in the safe position. For a cooling heat exchanger, loss of air must open the valve (fail-open) to maintain cooling.
187.Forgetting CSA B149.1 for gas: gas valves must be CSA certified and installed according to ventilation requirements. Failing to mention this standard in a response about gas valves is a common error.
188.Neglecting the packing gland: overtightening causes friction and hysteresis. Insufficient tightening causes leakage. Packing gland adjustment is a practical skill that is assessed.
189.Confusing relief valves and control valves: the relief valve is never used for regulation. It opens automatically at a predetermined pressure.
190.Not verifying material compatibility: 316 stainless steel trim is unsuitable for hydrochloric acid. Materials must be compatible with the fluid and temperature.

Summary

The control valve is the final control element; it converts the controller signal into flow.
The three main flow characteristics are linear, equal percentage, and quick opening. Equal percentage is the most commonly used.
Cv is the flow coefficient: Cv = Q × √(SG / ΔP) for liquids. Sizing must include a 20-30% margin.
Pneumatic diaphragm actuators are the most common; positioners improve accuracy and enable diagnostics.
Installation must respect flow direction, provide a bypass, and ensure accessibility.
Positioner calibration follows the sequence: zero, span, linearity, repeatability.
Key Canadian standards: Canadian Electrical Code, Part I (Rules 18-100, 18-152, 8-200), CSA B149.1 (natural gas and propane), CSA B51 (pressure equipment).
Safety valves and relief valves are distinct from control valves; they are tested periodically per IEC 61511.
Common diagnostics include friction, hysteresis, cavitation, and noise.

Review Questions (Self-Assessment)

204.Calculate the required Cv for a flow of 250 GPM of a liquid with SG = 1.1 and ΔP = 18 psi.
205.A globe valve has a rated Cv of 60. What is its typical rangeability and what is the minimum controllable flow?
206.Which flow characteristic would you choose for a level control valve where ΔP is constant? Justify your answer.
207.Name three installation requirements for a relief valve per CSA B51.
208.What is the difference between a fail-open and a fail-closed valve? Give an example of a process for each case.
209.A smart positioner reports 5% hysteresis. What are the probable causes and corrective actions?
210.For a gas with P1 = 100 psia and P2 = 40 psia, is the flow choked? Justify your answer.

This chapter covers the essential knowledge for the Red Seal exam in instrumentation and control. Practicing calculations and becoming familiar with Canadian standards are essential for success.

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free