Installation of Dry Pipe and Preaction Sprinkler Systems
Red Seal Practice study guide with diagrams.
Installation of Dry Pipe and Preaction Sprinkler Systems
Introduction
Dry pipe sprinkler systems and preaction systems are essential components of fire protection in buildings where ambient temperatures can drop below 4 °C (40 °F) or where accidental water damage would be catastrophic. Unlike wet systems that maintain water under pressure in all piping, these systems use pressurized air or nitrogen to control an alarm valve. This chapter covers operating principles, design requirements, air volume calculations, bypass devices (accelerators and exhausters), as well as the rules of the National Fire Code of Canada (NFC) and NFPA 13, as adopted in Canada.
Definitions and Fundamental Principles
Dry Pipe System
A dry pipe system is an automatic sprinkler system in which the piping is filled with pressurized air or nitrogen (supervisory pressure) rather than water. Water is held back upstream of a dry pipe valve. When a sprinkler opens, the air pressure drops, the valve opens, and water enters the piping to reach the open sprinkler.
Main components:
Preaction System
A preaction system is an automatic sprinkler system connected to a piping network containing air at atmospheric pressure or under low supervisory pressure, with a preaction valve controlled by a smoke, heat, or flame detector. Water is admitted into the piping only when a detector is activated (single interlock) or when a detector AND a sprinkler are both activated (double interlock).
Types of preaction systems:
Key Difference Between the Two Systems
| Characteristic | Dry Pipe | Preaction |
|---|---|---|
| Air pressure in piping | Supervisory pressure (typ. 140–350 kPa) | Atmospheric or low pressure (20–35 kPa) |
| Activation | Opening of a sprinkler | Detector (single interlock) or detector + sprinkler (double interlock) |
| Response time | Slower (air evacuation required) | Variable depending on type |
| Risk of accidental water damage | Low (requires an open sprinkler) | Very low (double interlock) |
| Typical use | Parking garages, unheated warehouses, loading docks | Computer rooms, archives, museums |
Dry Pipe Valve
Differential Clapper Principle
The dry pipe valve uses a differential clapper that maintains the balance between water pressure (upstream side) and air pressure (downstream side). The ratio of the clapper surface areas is typically 5:1 to 6:1. This means that for each unit of air pressure, the valve can withstand 5 to 6 units of water pressure.
Formula for calculating minimum air pressure:
P_air_min = (P_water_max) / (Differential ratio)
Where:
Example: If the maximum water pressure is 1,200 kPa and the differential ratio is 5.5:
P_air_min = 1,200 / 5.5 = 218 kPa
The supervisory air pressure must be maintained at least 20 kPa above P_air_min to prevent unintentional valve opening.
Valve Components
Operation During a Fire
Air Volume Calculation and Response Time
Response Time Requirement
The NFC (Article 3.2.5.14) and NFPA 13 (Section 7.2.3) require that water reach the most remote sprinkler within a maximum of 60 seconds for dry pipe systems. This time is measured from the opening of the sprinkler until water arrives at the sprinkler orifice.
Air Volume Calculation
The air volume in the piping determines the evacuation time. The total volume is calculated from the pipe diameters and lengths:
V_air = Σ (π × d² / 4) × L
Where:
Table of air volumes per metre of pipe (Schedule 40 steel pipe):
| Nominal Diameter (in) | Inside Diameter (mm) | Volume (L/m) |
|---|---|---|
| 1 | 26.6 | 0.556 |
| 1 ¼ | 35.1 | 0.968 |
| 1 ½ | 40.9 | 1.314 |
| 2 | 52.5 | 2.165 |
| 2 ½ | 62.7 | 3.088 |
| 3 | 77.9 | 4.766 |
| 4 | 102.3 | 8.219 |
| 6 | 154.1 | 18.650 |
Volume Limits for Systems Without an Accelerator
NFPA 13 (Article 7.2.3.6.2) limits the air volume to 3,785 L (1,000 US gal) for dry pipe systems without an accelerator. Beyond this volume, an accelerator or exhauster is required to meet the 60-second time limit.
Rule of Thumb for Calculating Evacuation Time
The air evacuation time can be estimated using the following formula:
t = V_air / Q_air
Where:
The air flow through an open sprinkler depends on the air pressure and the discharge coefficient (K) of the sprinkler. For a standard sprinkler K = 5.6 (80.6 in metric units), the air flow can be approximated by:
Q_air ≈ K × √(P_air)
Where P_air is in kPa and K is in L/min/√kPa.
Accelerators and Exhausters
Accelerator
The accelerator is a device that detects a rapid drop in air pressure in the piping (due to a sprinkler opening) and allows air or water to enter the intermediate chamber of the valve to speed up its opening. It reduces the response time of the system.
Operation:
Installation requirements:
Exhauster
The exhauster is a device that evacuates air from the piping in a controlled manner when water is admitted. It is installed at the end of the piping, often at the highest or most remote point.
Operation:
Types of exhausters:
Comparison: Accelerator vs. Exhauster
| Characteristic | Accelerator | Exhauster |
|---|---|---|
| Primary function | Accelerate valve opening | Evacuate air from the piping |
| Location | Near the alarm valve | End of the piping |
| Activation | Air pressure drop | Water arrival |
| Effect | Reduces initial response time | Reduces final fill time |
| Maintenance | Annual test required | Periodic inspection |
Sprinklers for Dry Pipe Systems
Dry Sprinklers
Dry sprinklers are used for pendants in dry pipe systems. They consist of an outer tube containing a fusible link element and an inner tube (or stem) that transmits the closing force. Water only enters the sprinkler when the fusible element melts.
Characteristics:
Installation requirements:
Temperature Ratings and Colours
| Temperature Rating (°C) | Classification | Liquid Colour (Bulb) |
|---|---|---|
| 57 | Ordinary | Orange |
| 68 | Ordinary | Red |
| 79 | Intermediate | Yellow |
| 93 | High | Green |
| 141 | High | Blue |
| 182 | Very High | Purple |
| 227 | Very High | Black |
Pipe Slopes and Drainage
Slope Requirement
The NFC (Article 3.2.5.15) and NFPA 13 (Article 7.2.6) require that dry pipe system piping be installed with a minimum slope to allow complete drainage:
Rule of thumb: The slope must allow water to drain completely by gravity to the drain points. Low points must be equipped with drain valves.
Drain Points
Each low point in the piping must be provided with a drain valve of at least 25 mm (1 in) diameter. Drain valves must be accessible and identified.
Consequences of Poor Drainage
Alarm and Supervision Devices
Water Motor Gong (Alarm Bell)
The water motor gong is operated by the flow of water into the intermediate chamber of the valve. Water passes through a 3.2 mm (1/8 in) orifice and drives a turbine that sounds the bell.
Requirements:
Pressure Switch
The pressure switch detects the pressure change in the intermediate chamber and sends an electrical signal to the fire alarm control panel. It must be ULC (Underwriters Laboratories of Canada) or cUL certified.
Valve Supervision Switch
A tamper switch (limit switch) must be installed on the main isolation valve to signal any unauthorized closure of the valve.
Air Compressors and Air Supply Systems
Air Compressor
The air compressor maintains the supervisory pressure in the piping. It must be sized to compensate for normal small leaks in the system.
Sizing requirements:
Nitrogen Supply
Nitrogen is increasingly used as a supervisory gas to reduce internal corrosion of the piping. Nitrogen is supplied by high-pressure cylinders with a pressure-reducing valve.
Advantages of nitrogen:
Typical Supervisory Pressure
| System Type | Supervisory Pressure |
|---|---|
| Dry pipe (air) | 140–350 kPa (depending on water pressure) |
| Dry pipe (nitrogen) | 140–350 kPa |
| Preaction (air) | 20–35 kPa (atmospheric +) |
| Preaction (nitrogen) | 20–35 kPa |
Preaction Systems: Design and Requirements
Preaction Valve
The preaction valve is an electrically or pneumatically actuated valve that controls the admission of water into the piping. It is typically a clapper valve or a motorized butterfly valve.
Components:
Single Interlock vs. Double Interlock
Single interlock:
Double interlock:
Special Requirements
National Fire Code of Canada (NFC) Rules
Article 3.2.5.14 — Dry Pipe Systems
The NFC requires that:
Article 3.2.5.15 — Slopes and Drainage
Article 3.2.5.16 — Preaction Systems
NFPA 13 — Key References
| NFPA 13 Section | Subject |
|---|---|
| 7.2.3 | Response time (60 s) |
| 7.2.3.6.2 | Maximum air volume without accelerator (3,785 L) |
| 7.2.6 | Slopes and drainage |
| 7.3 | Dry sprinklers |
| 8.2 | Preaction systems |
| 8.3 | Valves and components |
Practical Calculations for the Exam
Calculating Required Air Pressure
Formula: P_air = (P_water / R) + 20 kPa
Where:
Example: P_water = 1,100 kPa, R = 5.5
P_air = (1,100 / 5.5) + 20 = 200 + 20 = 220 kPa
Calculating Total Air Volume
Formula: V_total = Σ (V_unit × L)
Example: 50 m of 2 in pipe (2.165 L/m) + 30 m of 1 ½ in pipe (1.314 L/m)
V_total = (50 × 2.165) + (30 × 1.314) = 108.25 + 39.42 = 147.67 L
Verifying the 60-Second Time Limit
Formula: t = V_total / Q_air
Example: V_total = 147.67 L, Q_air = 40 L/s (sprinkler K = 80.6, P_air = 220 kPa)
Q_air = 80.6 × √220 = 80.6 × 14.83 = 1,195 L/min = 19.9 L/s
t = 147.67 / 19.9 = 7.4 seconds
This system easily meets the 60-second time limit.
Pitfalls to Avoid
Summary
Pitfalls to Avoid (Quick Recap)
| Pitfall | Consequence |
|---|---|
| Forgetting the 20 kPa margin | Insufficient air pressure → unintentional opening |
| Confusing L/min and L/s | Calculation errors in response time |
| Insufficient slope | Incomplete drainage → freezing and corrosion |
| Volume > 3,785 L without accelerator | NFPA 13 non-compliance |
| Standard sprinklers for pendants | Sprinklers not suitable for dry system |
| Single vs. double interlock | Different times and requirements |
Self-Assessment Questions
(Answer: (1,300 / 5.5) + 20 = 256 kPa)
(Answer: No, the maximum volume is 3,785 L. An accelerator is required.)
(Answer: 4 mm per metre, directed toward the valve or drain points.)
(Answer: Single interlock admits water upon detector activation alone; double interlock requires both detector activation AND the opening of a sprinkler.)
(Answer: The accelerator.)
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free