Heating, Ventilation, and Heat Recovery Systems
Red Seal Practice study guide with diagrams.
Heating, Ventilation, and Heat Recovery Systems
Introduction to the Chapter
This chapter covers the fundamental principles, components, calculations, and regulatory requirements related to heating, ventilation, and heat recovery systems, as assessed on the Red Seal exam for the Refrigeration and Air Conditioning Mechanic trade. You must master these concepts to diagnose, install, and maintain integrated systems that combine thermal comfort, indoor air quality, and energy efficiency.
Fundamental Principles of Heating
Thermal Loads and Energy Balances
Thermal load calculation is the foundation of any system sizing. The heating load represents the amount of heat that must be supplied to a space to maintain a design indoor temperature when the outdoor temperature is at its design minimum. The cooling load represents the heat that must be removed to maintain the same indoor temperature when the outdoor temperature is at its design maximum.
The basic formula for heat transmission through a wall is:
Q = U × A × ΔT
Where:
The total thermal resistance (R) is the inverse of the U-factor: R = 1/U. R-values of materials add in series. For example, a wall composed of brick (R = 0.35), insulation (R = 2.5), and gypsum board (R = 0.08) has a total resistance of 2.93 m²·°C/W, therefore U = 1/2.93 = 0.341 W/(m²·°C).
Sensible Heat and Latent Heat
Sensible heat causes a temperature change without a phase change. The formula is:
Q = m × c × ΔT
Where m is the mass in kg, c is the specific heat in kJ/(kg·°C), and ΔT is the temperature change in °C. For air, c ≈ 1.006 kJ/(kg·°C). For water, c = 4.186 kJ/(kg·°C).
Latent heat causes a phase change without a temperature change. For water, the latent heat of vaporization is approximately 2,257 kJ/kg at atmospheric pressure, and the latent heat of fusion is 334 kJ/kg.
Heating Degree-Days
Heating degree-days (HDD) are a measure used to estimate seasonal energy consumption. One degree-day is accumulated for each day where the average temperature is below 18 °C, with the difference being the number of degree-days. For example, a day with an average temperature of 5 °C accumulates 13 HDD. The simplified formula for estimating annual consumption is:
Annual consumption (kWh) = (HDD × U × A × 24) / 1000
Ventilation Systems
Ventilation Requirements According to the National Building Code
The National Building Code of Canada (NBC) specifies minimum ventilation rates for different occupancy types. For residential buildings, the minimum mechanical ventilation rate is 0.35 air changes per hour (ACH) or 7.5 L/s per person, whichever is greater. For commercial buildings, rates vary by use: 10 L/s per person for offices, 15 L/s for classrooms, and 20 L/s for restaurants.
The following table summarizes typical requirements:
| Occupancy Type | Minimum Ventilation Rate (L/s per person) | Minimum Air Change Rate (ACH) |
|---|---|---|
| Residential | 7.5 | 0.35 |
| Offices | 10 | — |
| Classrooms | 15 | — |
| Restaurants | 20 | — |
| Hospitals (patient rooms) | 25 | 6 |
| Laboratories | 20 | 8 |
Mechanical and Natural Ventilation
Mechanical ventilation uses fans to move air. Systems can be single-flow (exhaust-only or supply-only) or double-flow (combined exhaust and supply). Natural ventilation relies on pressure and temperature differences, but it is rarely sufficient for modern airtight buildings.
Balanced ventilation is essential to avoid negative or positive pressures in the building. Excessive negative pressure can cause backdrafting of combustion products from gas appliances, creating a risk of carbon monoxide poisoning. Excessive positive pressure can cause moisture infiltration into the building envelope.
Balancing Ventilation Systems
Balancing involves adjusting airflow rates in each branch of the duct network to meet design flow rates. The standard procedure includes:
The relationship between static pressure (Ps) and airflow (Q) in a duct system is: Ps ∝ Q². If you double the airflow, the static pressure quadruples. This relationship is crucial for understanding the effect of fan speed changes.
Heat Recovery Systems
Principles of Heat Recovery
Heat recovery in ventilation systems involves transferring heat from the exhaust (stale) air to the incoming fresh air. This reduces the heating or cooling load of the building. The efficiency of a heat recovery unit is expressed by its sensible effectiveness:
η = (T₂ - T₁) / (T₃ - T₁) × 100 %
Where:
Types of Heat Recovery Units
Plate Heat Recovery Unit (Plate Heat Exchanger)
The plate heat recovery unit is the simplest type. Fresh air and exhaust air flows travel through adjacent channels separated by metal or plastic plates. Heat is transferred through the plates by conduction. Typical effectiveness is 50 to 70%. There is no moisture transfer, only sensible heat. Advantages: no moving parts, low maintenance. Disadvantages: risk of frost formation at low temperatures, requires a bypass for the summer season.
Rotary Heat Recovery Unit (Thermal Wheel)
The thermal wheel is a rotating cylinder composed of a metal or fibre matrix. The wheel rotates slowly (10 to 20 revolutions per minute) between the two air streams. The matrix absorbs heat from the exhaust air and releases it to the fresh air. Effectiveness can reach 75 to 85%. Some wheels are hygroscopic and also transfer moisture (latent heat). Advantages: high efficiency, possible moisture transfer. Disadvantages: moving parts, risk of cross-contamination (generally less than 5%), maintenance of motor and belts.
Heat Pipe Recovery Unit
The heat pipe is a sealed tube containing a refrigerant fluid. Heat from the exhaust air evaporates the fluid at the hot end of the tube. The vapour travels to the cold end where it condenses, releasing heat to the fresh air. The condensate returns by gravity or capillary action. Effectiveness is 50 to 70%. Advantages: no moving parts, no cross-contamination. Disadvantages: limited effectiveness, requires inclination for condensate return.
Glycol Run-Around Loop Recovery Unit
This system uses two coils (one in the exhaust air stream, the other in the fresh air stream) connected by a liquid loop (glycol-water solution). A pump circulates the liquid. Effectiveness is 40 to 60%. Advantages: coils can be located far apart from each other, no cross-contamination. Disadvantages: lower effectiveness, requires a pump and expansion tank.
| Type of Heat Recovery Unit | Typical Sensible Effectiveness | Moisture Transfer | Moving Parts | Cross-Contamination |
|---|---|---|---|---|
| Plate | 50-70% | No | No | Negligible |
| Rotary | 75-85% | Possible (if hygroscopic) | Yes | 1-5% |
| Heat pipe | 50-70% | No | No | None |
| Glycol run-around loop | 40-60% | No | Yes (pump) | None |
Frost Formation in Heat Recovery Units
Frost formation occurs when the temperature of the exhaust air drops below the freezing point of water. Water vapour from the exhaust air freezes on the heat exchanger surfaces, obstructing airflow and reducing effectiveness. Defrost strategies include:
The frost threshold depends on the relative humidity of the exhaust air. For a relative humidity of 30% at 21 °C, frost formation begins at approximately -5 °C outdoor temperature. For 50% relative humidity, frost formation begins at approximately 0 °C.
Heat Pumps and Hybrid Systems
Air-to-Air Heat Pumps
Air-to-air heat pumps are heating and cooling systems that transfer heat between indoor and outdoor air. The coefficient of performance (COP) is the ratio of heat delivered to electrical energy consumed. A COP of 3 means that for 1 kW of electricity consumed, 3 kW of heat is delivered.
COP decreases as outdoor temperature drops. At -25 °C, the COP of a conventional heat pump can drop to 1.5 or less. Cold climate heat pumps maintain a COP above 2 down to -25 °C.
Bivalent Systems
A bivalent system combines a heat pump with a backup heating system (electric, gas, or hydronic). The balance point is the outdoor temperature at which the heat pump can no longer supply the full heating load. Below this point, the backup heating takes over.
Calculating the balance point requires knowing the building heating load at the design temperature and the heat pump capacity at different temperatures. For example, if the heating load is 10 kW at -30 °C and the heat pump delivers 8 kW at -10 °C, the balance point is at -10 °C.
Canadian Electrical Code Requirements
The Canadian Electrical Code, Part I (CE Code) (C22.1) applies to all electrical installations, including heating and ventilation systems. Relevant rules include:
For heat recovery systems, the code requires that fan motors be protected against overloads in accordance with Rule 28-308.
CSA B149.1 Code Requirements
CSA B149.1, Natural Gas and Propane Installation Code applies to gas-fired heating appliances. Relevant requirements include:
The interaction between mechanical ventilation and gas appliances is critical. Excessive exhaust ventilation can create a negative pressure that prevents the venting of combustion products. The code requires that ventilation systems be designed to maintain a slightly positive or neutral pressure in spaces containing gas appliances.
Installation and Commissioning Procedures
Installation of Heat Recovery Units
The installation of an air-to-air heat recovery ventilator (HRV) must follow these steps:
Commissioning and Verification
Commissioning includes:
The duct leakage test is performed by pressurizing the duct system to 250 Pa and measuring the leakage. The maximum allowable leakage is 5% of the total airflow for sealed ducts, according to ASHRAE standards.
Diagnostics and Troubleshooting
Common Heat Recovery Unit Problems
| Symptom | Probable Cause | Corrective Action |
|---|---|---|
| Excessive frost formation | Very low outdoor temperature, high indoor humidity | Activate defrost, reduce humidity |
| Insufficient airflow | Clogged filters, obstructed ducts, faulty fan | Replace filters, clean ducts, check fan |
| Reduced effectiveness | Dirty heat exchanger, bypass open | Clean heat exchanger, check bypass position |
| Abnormal noise | Worn fan bearing, wheel imbalance | Replace bearing, balance wheel |
| Excessive condensation | Clogged drain, insufficient trap | Clean drain, check trap |
Measuring Effectiveness Under Actual Conditions
To measure the actual effectiveness of a heat recovery unit, you must measure temperatures at all four points (fresh air entering, fresh air leaving, exhaust air entering, exhaust air leaving) and apply the sensible effectiveness formula. Measurements must be taken at steady state, meaning after at least 15 minutes of stable operation.
Practical Calculations for the Exam
Example 1: Heating Load Calculation
A warehouse measuring 20 m × 15 m × 4 m has 200 mm concrete walls (U = 1.7 W/(m²·°C)) and an insulated roof (U = 0.4 W/(m²·°C)). The design indoor temperature is 18 °C and the design outdoor temperature is -30 °C. Calculate the transmission heating load.
Solution:
Wall area: 2 × (20 × 4) + 2 × (15 × 4) = 160 + 120 = 280 m²
Roof area: 20 × 15 = 300 m²
Q_walls = U × A × ΔT = 1.7 × 280 × (18 - (-30)) = 1.7 × 280 × 48 = 22,848 W
Q_roof = 0.4 × 300 × 48 = 5,760 W
Q_total = 22,848 + 5,760 = 28,608 W ≈ 28.6 kW
Example 2: Heat Recovery Unit Effectiveness
A plate heat recovery unit has the following temperatures: fresh air entering = -10 °C, fresh air leaving = 12 °C, exhaust air entering = 22 °C. Calculate the sensible effectiveness.
Solution:
η = (T₂ - T₁) / (T₃ - T₁) × 100 %
η = (12 - (-10)) / (22 - (-10)) × 100 %
η = 22 / 32 × 100 % = 68.75%
Example 3: Required Ventilation Airflow
A residential building has a floor area of 200 m² and a ceiling height of 2.5 m. Calculate the minimum required ventilation airflow.
Solution:
Volume = 200 × 2.5 = 500 m³
Air change rate: 0.35 ACH
Airflow = 500 × 0.35 / 3600 = 0.0486 m³/s = 48.6 L/s
The per-person rate (7.5 L/s) applies if the number of occupants is known. For 4 occupants: 4 × 7.5 = 30 L/s. The higher value (48.6 L/s) applies.
Pitfalls to Avoid
Summary
Mastering these concepts will enable you to succeed on Red Seal exam questions covering heating, ventilation, and heat recovery systems. Pay particular attention to units, conversion factors, and regulatory requirements, as these elements are frequently tested.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free