Chapter IX

Air Conditioning and Air Handling Systems

Red Seal Practice study guide with diagrams.

Air Conditioning and Air Handling Systems

Chapter Introduction

This chapter covers the fundamental principles of air conditioning and air handling systems as assessed on the Red Seal exam for the refrigeration and air conditioning mechanic trade. You must master not only thermodynamic cycles, but also duct sizing, heat load calculations, applied psychrometrics, and Canadian regulatory requirements. This chapter is structured to follow the logical progression of a system analysis: from heat load to equipment selection, then to air distribution and commissioning.


1. Fundamental Principles of Air Conditioning

1.1 Definition and Objectives of Air Conditioning

Air conditioning is the process of treating air to simultaneously control its temperature, humidity, cleanliness, and distribution, in order to maintain specific comfort conditions or process conditions. For the exam, remember that air conditioning is not limited to cooling: it encompasses heating, ventilation, filtration, humidification, and dehumidification.

The four fundamental psychrometric quantities you must know:

QuantitySymbolUnitDefinition
Dry-bulb temperatureDBT°CTemperature measured by an ordinary thermometer
Wet-bulb temperatureWBT°CTemperature measured by a thermometer whose bulb is wrapped in a wet wick
Relative humidityRH%Ratio of the partial pressure of water vapor to the saturation pressure at the same temperature
Absolute humidityωg/kg of dry airMass of water vapor per kilogram of dry air

1.2 Thermal Comfort

Thermal comfort is defined by ASHRAE Standard 55 as the state of mind that expresses satisfaction with the thermal environment. The factors influencing comfort are:

Dry-bulb temperature (recommended: 22 to 26 °C in summer)
Relative humidity (recommended: 30 to 60 %)
Air velocity (recommended: 0.15 to 0.25 m/s in occupied zones)
Mean radiant temperature of surfaces
Metabolic activity level (in met)
Clothing insulation (in clo)

For the exam, remember the typical summer comfort zone: 24 °C ± 2 °C and 50 % RH ± 10 %. In winter, the recommended temperature is 21 °C ± 2 °C.

1.3 The Air Conditioning Cycle — Thermodynamic Review

The mechanical refrigeration cycle used in air conditioning is the vapor compression cycle. The four main components are:

21.The compressor: draws in low-pressure vapor and compresses it to high pressure
22.The condenser: rejects heat from the refrigerant to the outdoors
23.The expansion device (TXV or capillary tube): lowers the pressure and temperature of the refrigerant
24.The evaporator: absorbs heat from the air or water being cooled

In a direct expansion (DX) air conditioning system, the evaporator is placed directly in the air handling unit. In a chilled water system, the evaporator cools water (typically to 6.7 °C) which then circulates to the coils of air handling units.

Air Handling Unit (AHU) — Airflow path, fan, coils, filters Air Handling Unit (AHU) — Airflow Path AHU Casing (Insulated Enclosure) AIR RETURN (Return Air) Air drawn from the space — mixed with fresh air inlet FILTERS (Filters) MERV 8–13 (pre-filter + final) COOLING COIL (Cooling Coil) chilled water return HEATING COIL (Heating Coil) hot water return FAN (Supply Fan) M motor SUP- PLY (Supply) to space ~22°C return ~12°C supply static pressure Typical sequence: return air → filtration → cooling → heating → fan → distribution Air particle

Sensible heat calculation for an air flow rate:

Q sensible = 1.23 × flow rate (L/s) × ΔT (K)

Where 1.23 is the product of air density (1.2 kg/m³) and specific heat (1.026 kJ/kg·K), converted for flow rate units in L/s. This factor must be memorized.

Latent heat calculation:

Q latent = 3.0 × flow rate (L/s) × Δω (g/kg)

Where 3.0 is the latent heat of vaporization factor for water at room temperature (≈ 2500 kJ/kg) converted.


2. Applied Psychrometrics

2.1 The Psychrometric Chart

Psychrometric Chart — Heating, Cooling and Humidification Psychrometric Chart — Air Conditioning Processes Sensible heating Sensible cooling Humidification Cooling + dehumidification State point Dry bulb temperature (°C) Specific humidity (g/kg') 10 15 20 25 30 35 40 45 50 55 5 10 15 20 25 30 35 RH 90% RH 50% A B Heating sensible C D Cooling sensible E F Humidi- fication G H Cooling + dehumidi. Key Points (Red Seal) • Sensible heating: RH decreases, DBT increases, absolute humidity constant. • Sensible cooling: RH increases, DBT decreases, no change in humidity. • Humidification: Adding steam or water spray. RH and absolute humidity ↑. • Cooling + dehumidification: Cold coil below the dew point. Condensation and moisture removal. • Saturation line: RH = 100% Fog / droplet formation. Q = m × Cp × ΔT (sensible heat) Q = m × Δh (total heat) The psychrometric chart is an essential tool for diagnosing and troubleshooting HVAC systems — Red Seal

The psychrometric chart is the essential graphical tool for the air conditioning mechanic. It represents the thermodynamic properties of moist air at a given atmospheric pressure (typically 101.325 kPa at sea level). The main lines:

Dry-bulb temperature lines (vertical)
Wet-bulb temperature lines (diagonal, descending)
Relative humidity lines (curved)
Humidity ratio lines (horizontal)
Specific volume lines (diagonal)
Enthalpy lines (diagonal, parallel to WBT lines)

2.2 Fundamental Psychrometric Processes

ProcessLine on the ChartApplication
Sensible heatingHorizontal to the rightHeating coil
Sensible coolingHorizontal to the leftCooling coil (dry air)
Adiabatic humidificationConstant enthalpy lineAir washer, steam humidifier
Dehumidification by coolingCurve downward and to the leftCold coil with condensation
Mixing of two air streamsStraight line between the two pointsReturn air/outdoor air mixing

Dew point: the temperature at which air becomes saturated (RH = 100 %) if cooled at constant pressure. It is the coil surface temperature below which condensation will occur.

Sensible Heat Factor (SHF):

SHF = Q sensible / (Q sensible + Q latent)

An SHF of 0.75 means that 75 % of the total heat load is sensible. This factor determines the slope of the condition line (or sensible heat factor line) on the psychrometric chart, which connects the return air point to the supply air point.

2.3 Typical Psychrometric Calculations for the Exam

Example 1 — Air Mixing:

You mix 600 L/s of return air at 24 °C DBT, 50 % RH with 200 L/s of outdoor air at 32 °C DBT, 60 % RH. The mixture temperature is:

DBT mixture = (600 × 24 + 200 × 32) / (600 + 200) = (14,400 + 6,400) / 800 = 26 °C

Example 2 — Dehumidification:

A coil cools 1,000 L/s of air from 26 °C DBT, 21 °C WBT to 12 °C DBT, 11 °C WBT. The amount of condensed water is:

Δω = ω₁ − ω₂ = 13.5 g/kg − 8.0 g/kg = 5.5 g/kg

Mass flow rate of air = 1,000 L/s × 1.2 kg/m³ / 1,000 = 1.2 kg/s

Condensed water = 1.2 kg/s × 5.5 g/kg = 6.6 g/s = 23.8 kg/h

Common trap: do not confuse the 1.23 factor (sensible heat) with the 3.0 factor (latent heat). Always check the units of the air flow rate.


3. Heat Load Calculations

3.1 Calculation Methodology

Heat load calculations follow the method from the ASHRAE Handbook — Fundamentals (RTS — Radiant Time Series method for cooling loads). For the exam, you must know the components of the load:

External sensible loads:

Solar gains through glazing (function of orientation, glazing type, shading)
Transmission through opaque walls (walls, roof): Q = U × A × ΔT equivalent
Outdoor air infiltration
Ventilation (required outdoor air)

Internal sensible loads:

Occupants: approximately 75 W sensible per person (sedentary activity)
Lighting: installed power × utilization factor × diversity factor
Electrical equipment and motors
Cooking appliances and processes

Latent loads:

Occupants: approximately 55 W latent per person (sedentary activity)
Infiltration and ventilation (humidity difference)
Processes producing water vapor

3.2 Typical Thermal Transmission Coefficients (U)

ElementTypical U value (W/m²·K)
Insulated exterior wall (R-20)0.30
Insulated roof (R-30)0.20
Double sealed glazing2.8
Triple glazing with low-emissivity coating1.6
Solid wood door2.2

Golden rule: the lower the U value, the better the insulation. Thermal resistance R = 1/U.

3.3 Ventilation and Indoor Air Quality

Standard ASHRAE 62.1 (Ventilation for Acceptable Indoor Air Quality) is the reference. For commercial buildings, the required outdoor air flow rate is calculated using the zone ventilation method:

Vbz = Rp × Pz + Ra × Az

Where:

Rp = air flow rate per person (L/s·person)
Pz = number of people in the zone
Ra = air flow rate per unit area (L/s·m²)
Az = zone area (m²)

Typical values for an office: Rp = 2.5 L/s·person, Ra = 0.3 L/s·m².

Minimum requirement: the National Building Code of Canada (NBC) requires a minimum of 8 L/s per person for spaces where occupants are sedentary, or 0.35 air changes per hour, whichever is greater.


4. Air Handling Systems

4.1 System Classification

System TypeDistribution FluidAdvantagesDisadvantages
All-air (constant volume)AirGood humidity control, centralized maintenanceLarge ductwork
All-air (variable volume — VAV)AirEnergy savings, individual controlRisk of stratification, need for reheat
Air-water (fan coils)Air + waterReduced ductwork, local controlPossible condensation, multiple maintenance points
All-water (fan coils)WaterVery compactNo mechanical ventilation, freeze risk
Direct expansion (DX)RefrigerantEfficient, compactLimited line lengths, limited humidity control

4.2 The Air Handling Unit (AHU)

The air handling unit is the heart of the system. Its components, in air flow order:

97.Mixing section: outdoor air, return air, and exhaust air dampers
98.Filters: pre-filters (MERV 8) and final filters (MERV 13 or higher)
99.Cooling coil: chilled water or direct expansion
100.Heating coil: hot water, electric, or steam
101.Humidifier: steam, evaporative, or atomizing
102.Supply fan: centrifugal or axial
103.Silencer sections and acoustic attenuation

Exam trap: the order of components is crucial. The cooling coil must be placed before the heating coil and after the filters. The humidifier is generally placed after the coils.

4.3 Fans

The two main families of fans:

Centrifugal fans:

Forward-curved blades: high flow rate, moderate static pressure, low efficiency
Backward-curved blades: high efficiency, high static pressure, non-overloading
Radial blades: for high-pressure applications and abrasive materials

Axial fans:

Propeller: low pressure, high flow rate
Tubular: medium pressure
Variable pitch: for large flow rates at variable pressure

Fan Laws (at constant density):

Flow rate Q ∝ rotational speed N
Pressure P ∝ N²
Power W ∝ N³

Example: If the rotational speed increases by 10 %, the flow rate increases by 10 %, the pressure increases by 21 % (1.1² = 1.21), and the power increases by 33 % (1.1³ = 1.331). This is a classic exam trap.

4.4 Air Ducts

Sizing methods:

122.Constant velocity method: you set a maximum velocity in each section (e.g., 5 m/s in the main duct, 3 m/s in branches). Simple but can unbalance the system.
123.Constant pressure loss method (or constant friction method): ducts are sized to maintain a constant pressure loss per metre (typically 0.8 Pa/m). This is the most commonly used method.
124.Static regain method: ducts are sized so that static pressure is the same at each outlet. More accurate but more complex.

Pressure loss in ducts:

ΔP = f × (L/D) × (ρ × V² / 2)

Where f is the friction factor (dependent on Reynolds number and roughness), L the length, D the hydraulic diameter, ρ the density, and V the velocity.

Equivalent diameter for a rectangular duct:

De = 1.30 × [(a × b)⁵ / (a + b)²]^(1/8)

Where a and b are the dimensions of the rectangular duct in mm. This formula is used to use the pressure loss charts for circular ducts.

Recommended duct velocities:

ApplicationMain duct (m/s)Branch (m/s)
Residential3 to 42 to 3
Commercial (quiet)5 to 63 to 4
Commercial (standard)7 to 95 to 6
Industrial10 to 137 to 10

5. Air Conditioning Equipment

5.1 Chilled Water Chillers

Water Chiller — Chilled Water Loop Water Chiller — Chilled Water Loop CHILLER (Chiller) Evaporator (Evaporator) Refrigerant R-134a PRIMARY PUMP (Primary Pump) Constant flow FAN COIL UNIT (Fan Coil Unit) Cooling Coil (Cooling Coil) COOLING TOWER (Cooling Tower) Condenser CONDENSER PUMP (Condenser Pump) SUPPLY — CHILLED WATER (Supply — Chilled Water) RETURN — WARM WATER (Return — Warm Water) CONDENSER LOOP (Condenser Loop) 6°C (43°F) 12°C (54°F) KEY POINTS • Evaporator absorbs heat from the water • Condenser rejects heat to the tower • Primary pump = constant flow LEGEND Chilled water (supply) Warm water (return) Condenser water Chilled water loop system — Interprovincial Red Seal standards

Chilled water chillers produce cold water (typically at 6.7 °C) to supply the coils of AHUs and fan coils. Two main types:

Air-cooled chillers:

Condenser cooled by ambient air
Installed outdoors
Lower energy efficiency (typical EER of 9 to 11)
No cooling tower required

Water-cooled chillers:

Condenser cooled by water from a cooling tower
Installed indoors
Higher efficiency (typical EER of 12 to 16)
Requires a cooling tower and pump

Coefficient of Performance (COP):

COP = Cooling capacity (kW) / Power input (kW)

EER (Energy Efficiency Ratio) = COP × 3.412 (in BTU/h per watt)

Exam trap: COP is dimensionless (kW/kW), while EER is in BTU/(h·W). Never confuse them.

5.2 Cooling Towers

The cooling tower rejects condenser heat to the atmosphere through evaporation. Types:

Natural draft: large chimney, air flow by natural convection
Mechanical draft: axial or centrifugal fan (most common)
Cross-flow: air flows horizontally through the falling water
Counter-flow: air rises vertically against the downward-flowing water

Operating parameters:

Approach: difference between the leaving cold water temperature and the ambient wet-bulb temperature (typically 3 to 5 °C)
Range: difference between the entering hot water temperature and the leaving cold water temperature (typically 5 to 10 °C)

Example: Outdoor air at 28 °C DBT, 22 °C WBT. A tower with an approach of 4 °C will produce water at 26 °C. If the range is 6 °C, the hot water will enter at 32 °C.

Freeze consideration: in northern climates, cooling towers must be protected against freezing. Measures include: water bypass, basin heating, fan speed control, and automatic drain.

5.3 Evaporative Condensers

The evaporative condenser combines the condenser and cooling tower into a single unit. The refrigerant circulates directly through coils that are sprayed with water and swept by air. The evaporated water absorbs heat from the refrigerant. Advantages: compactness, high efficiency. Disadvantages: water quality maintenance, corrosion risk.

5.4 Rooftop Units (RTU)

Rooftop units (RTUs) are self-contained systems installed on the roof, containing the compressor, condenser, evaporator, fans, and filters in a single enclosure. They are factory-fabricated and only require electrical connection and ductwork. Typical capacities: from 3 to 100 tons of refrigeration.

1 ton of refrigeration = 12,000 BTU/h = 3.517 kW


6. Control and Regulation

6.1 Control Strategies

Temperature control in a chilled water system is achieved by:

172.Chilled water valve control: the valve modulates the water flow through the coil based on the supply air temperature or zone temperature
173.Bypass damper control: a portion of the air bypasses the coil
174.Fan speed variation control: for VAV systems

Typical AHU control sequence:

Heating: hot water valve modulates from 0 to 100 %
Cooling: chilled water valve modulates from 0 to 100 %
The two never operate simultaneously (except during dehumidification)

6.2 Sensors

SensorMeasurementTypical Accuracy
ThermistorTemperature± 0.2 °C
RTD (Pt100)Temperature± 0.1 °C
Capacitive humidity sensorRelative humidity± 2 %
Differential pressure sensorPressure± 0.5 % of scale
Hot wire anemometerAir velocity± 2 %

6.3 Free Cooling Sequence

Free cooling (economizer) uses outdoor air to cool the building when its temperature is lower than the return air temperature. Two strategies:

Dry-bulb economizer: compares outdoor DBT to a threshold (e.g., 18 °C)
Enthalpy economizer: compares the enthalpy of outdoor air to that of return air

The enthalpy economizer is more accurate because it accounts for humidity. The National Energy Code of Canada for Buildings (NECB) requires economizers on systems over 35 kW (10 tons) in most Canadian climates.


7. Commissioning and Troubleshooting

7.1 Commissioning Procedure

Commissioning is the process of verifying that all systems operate in accordance with specifications. Steps:

190.Pre-verification: visual inspection, verification of electrical and mechanical connections
191.Operational tests: start-up of each piece of equipment individually
192.Air balancing (TAB — Testing, Adjusting and Balancing): measurement of air flow rates at each diffuser and damper
193.Water balancing: measurement of water flow rates in each coil
194.Control adjustment: sensor calibration, verification of sequences
195.Performance measurements: verification of temperatures, pressures, humidities
196.Documentation: commissioning report, operation manuals

7.2 Common Troubleshooting

Symptom: insufficient air flow

Dirty filters (excessive pressure drop)
Loose or worn fan belt
Obstructed ducts or closed dampers
Incorrect fan speed
System static pressure too high

Symptom: supply air temperature too high

Insufficient refrigerant charge (undercharge)
Chilled water valve stuck or faulty
Chilled water too warm (undersized chiller)
Dirty or frozen coil

Symptom: excessive humidity

Undersized cooling coil
Chilled water temperature too high
Air flow rate too high through the coil
System SHF too high relative to the load

7.3 Heat Balances

Cooling coil balance:

Q total = Q sensible + Q latent

Q total = mass flow rate of air × (h₁ − h₂)

Where h₁ and h₂ are the enthalpies of the air entering and leaving the coil.

Condenser balance:

Q condenser = Q evaporator + W compressor

This relationship is fundamental. If the compressor consumes 10 kW and the evaporator absorbs 40 kW, the condenser must reject 50 kW.


8. Applicable Canadian Codes and Standards

8.1 The Canadian Electrical Code (CE Code)

The Canadian Electrical Code, Part I (C22.1) applies to all electrical installations. Key points for air conditioning systems:

Rule 8-200: calculation of electrical demand for motors — the demand is based on the highest rated power plus 25 % of the largest motor added to the sum of the other motors
Rule 26-250: motor overload protection — the protective device must be set at 125 % of the full-load current for continuous duty motors
Rule 26-252: short-circuit protection — the fuse or circuit breaker must be sized according to Table 29 of the CE Code

Exam trap: the CE Code requires an accessible disconnecting means within 3 m of the equipment for motors and air conditioning appliances (Rule 28-600).

8.2 The National Building Code of Canada (NBC)

The NBC (National Building Code of Canada) contains ventilation, fire safety, and energy efficiency requirements. Relevant sections:

Section 3.2: fire safety — ducts must be made of non-combustible materials in high-rise buildings
Section 6.2: ventilation — minimum outdoor air flow requirements
Section 9.32: ventilation of small buildings

8.3 The National Energy Code of Canada for Buildings (NECB)

The NECB (National Energy Code of Canada for Buildings) imposes energy efficiency requirements:

Minimum chiller efficiency based on capacity (minimum COP)
Economizer requirement for systems over 35 kW
Duct and pipe insulation
Lighting control and heat recovery

8.4 CSA Standard B52

Standard CSA B52 (Mechanical Refrigeration Code) governs the installation of refrigeration systems. Key points:

Refrigerant classification based on toxicity and flammability (Groups A1, A2, A3, B1, etc.)
Refrigerant charge limits based on occupancy classification
Ventilation requirements for machinery rooms
Mandatory safety devices (pressure switches, relief valves, etc.)

8.5 CSA Standard B149.1

Standard CSA B149.1 (Natural Gas and Propane Installation Code) applies to gas-fired heating systems that are part of air handling. Key points:

Article 5.4: ventilation of gas appliances — appliances must have adequate combustion air supply
Article 8.2: venting of combustion products
Minimum clearance requirements around appliances

9. Energy Efficiency and Sustainability

9.1 Performance Indicators

IndicatorDefinitionApplication
EERBTU/h of cooling per watt consumedDX units
COPkW of cooling per kW consumedChillers, heat pumps
IPLVIntegrated Part Load Value — weighted efficiency at part loadChillers
kW/tonPower consumed per ton of refrigerationQuick comparison
SCOPSeasonal COP — seasonal efficiencyHeat pumps

Typical values for the exam:

Air-cooled chiller: COP of 2.8 to 3.2
Water-cooled chiller: COP of 4.5 to 6.5
Residential DX unit: SEER of 13 to 22
Geothermal heat pump: COP of 3.5 to 5.0

9.2 Heat Recovery

Heat recovery systems transfer energy from exhaust air to incoming outdoor air. Types:

Thermal wheel (enthalpy wheel): transfers heat and humidity, efficiency of 60 to 80 %
Plate heat exchanger: transfers sensible heat only, efficiency of 50 to 70 %
Heat pipe: passive transfer through phase change, efficiency of 40 to 60 %
Run-around loop (glycol loop): flexible, efficiency of 40 to 50 %

Heat exchanger efficiency calculation:

ε = (T outdoor outlet − T outdoor inlet) / (T exhaust inlet − T outdoor inlet) × 100 %

Example: Outdoor air at −10 °C, exhaust air at 22 °C. The outdoor air leaves at 12 °C. Efficiency = (12 − (−10)) / (22 − (−10)) × 100 % = 22 / 32 × 100 % = 68.75 %.


10. Safety and Environment

10.1 Refrigerants and the Environment

Refrigerants are classified according to their GWP (Global Warming Potential) and ODP (Ozone Depletion Potential):

RefrigerantTypeGWP (100 years)ODPStatus
R-22HCFC1,8100.055Phase-out
R-410AHFC2,0880In transition
R-134aHFC1,4300In transition
R-32HFC6750Accepted
R-454BHFO4660New
R-290 (propane)HC30Flammable A3
R-717 (ammonia)Natural00Toxic B2

The Ozone-depleting Substances and Halocarbon Alternatives Regulations (Government of Canada) requires:

Mandatory technician certification (Section 3 exam of the Regulations)
Record keeping of refrigerant quantities used
Mandatory recovery before opening any circuit
Prohibition of intentional refrigerant release

10.2 Risks Related to Air Handling Systems

Legionnaires' disease: cooling towers and humidifiers can promote the growth of Legionella bacteria. Maintenance: chemical water treatment, regular cleaning, water temperature control (maintain < 20 °C or > 60 °C)
Indoor air quality: adequate filtration, humidity control (avoid > 60 % RH to prevent mold)
Mechanical safety: guards on pulleys and belts, lockout/tagout before intervention
Electrical safety: compliance with the CE Code, grounding verification, use of personal protective equipment

10.3 Lockout/Tagout

Lockout/tagout is mandatory before any intervention on an air conditioning system. Procedure:

287.Identify all energy sources (electrical, mechanical, pneumatic, hydraulic)
288.Notify affected persons
289.Shut down the equipment
290.Isolate all energy sources
291.Apply locks and tags
292.Dissipate residual energy (capacitors, springs, pressure)
293.Verify absence of voltage with a voltmeter
294.Perform the intervention
295.Remove locks and return to service

Traps to Avoid

298.Confusing the 1.23 and 3.0 factors in load calculations — the first is for sensible heat, the second for latent heat
299.Forgetting that COP is dimensionless while EER is in BTU/(h·W)
300.Applying fan laws without checking air density — the laws only apply at constant density
301.Confusing wet-bulb temperature and dew point — WBT is always greater than or equal to the dew point
302.Neglecting the latent load of occupants — it represents approximately 40 % of the total occupant load
303.Placing the humidifier before the cooling coil — the correct order is: filters → cooling coil → heating coil → humidifier → fan
304.Sizing a duct with the constant velocity method without checking pressure losses — this can create imbalances
305.Forgetting the diversity factor in electrical load calculations — not all equipment operates simultaneously
306.Confusing the requirements of the CE Code and the NBC — the CE Code deals with electricity, the NBC with construction
307.Not checking refrigerant and oil compatibility — R-410A requires POE oil, not mineral oil
308.Ignoring external static pressure when selecting a fan — it must include ducts, coils, filters, and diffusers
309.Calculating air mixing with wet-bulb temperatures instead of dry-bulb temperatures — mixing is done on DBT and absolute humidity, not WBT

Summary

This chapter has presented the essential knowledge to pass the "Air Conditioning and Air Handling Systems" section of the Red Seal exam. Here are the key points to remember:

313.Psychrometrics: master the psychrometric chart, the four fundamental processes (heating, cooling, humidification, dehumidification) and the calculation factors 1.23 and 3.0.
314.Heat loads: know the sensible and latent components, internal and external, and the calculation method according to ASHRAE.
315.Systems: distinguish all-air, air-water, all-water, and DX systems, and know the advantages and disadvantages of each.
316.Fans: correctly apply the fan laws (Q ∝ N, P ∝ N², W ∝ N³) and select the appropriate type.
317.Ducts: use the constant friction method for sizing and check recommended velocities.
318.Equipment: know chillers, cooling towers, evaporative condensers, and rooftop units, as well as their operating parameters (approach, range).
319.Control: understand control sequences, sensors, and economizer strategies.
320.Codes: the CE Code (Rules 8-200, 26-250, 28-600), the NBC (Section 6.2), the NECB, CSA B52, and CSA B149.1 are the key regulatory references.
321.Energy efficiency: know how to calculate and interpret COP, EER, IPLV, and kW/ton.
322.Safety: lockout/tagout, refrigerant management, and Legionella prevention are professional responsibilities.

For the exam, practice solving air mixing problems, coil heat balance calculations, and duct sizing. Speed and accuracy in these calculations make the difference between a passing grade and an excellent one.

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free