Air Conditioning and Air Handling Systems
Red Seal Practice study guide with diagrams.
Air Conditioning and Air Handling Systems
Chapter Introduction
This chapter covers the fundamental principles of air conditioning and air handling systems as assessed on the Red Seal exam for the refrigeration and air conditioning mechanic trade. You must master not only thermodynamic cycles, but also duct sizing, heat load calculations, applied psychrometrics, and Canadian regulatory requirements. This chapter is structured to follow the logical progression of a system analysis: from heat load to equipment selection, then to air distribution and commissioning.
1. Fundamental Principles of Air Conditioning
1.1 Definition and Objectives of Air Conditioning
Air conditioning is the process of treating air to simultaneously control its temperature, humidity, cleanliness, and distribution, in order to maintain specific comfort conditions or process conditions. For the exam, remember that air conditioning is not limited to cooling: it encompasses heating, ventilation, filtration, humidification, and dehumidification.
The four fundamental psychrometric quantities you must know:
| Quantity | Symbol | Unit | Definition |
|---|---|---|---|
| Dry-bulb temperature | DBT | °C | Temperature measured by an ordinary thermometer |
| Wet-bulb temperature | WBT | °C | Temperature measured by a thermometer whose bulb is wrapped in a wet wick |
| Relative humidity | RH | % | Ratio of the partial pressure of water vapor to the saturation pressure at the same temperature |
| Absolute humidity | ω | g/kg of dry air | Mass of water vapor per kilogram of dry air |
1.2 Thermal Comfort
Thermal comfort is defined by ASHRAE Standard 55 as the state of mind that expresses satisfaction with the thermal environment. The factors influencing comfort are:
For the exam, remember the typical summer comfort zone: 24 °C ± 2 °C and 50 % RH ± 10 %. In winter, the recommended temperature is 21 °C ± 2 °C.
1.3 The Air Conditioning Cycle — Thermodynamic Review
The mechanical refrigeration cycle used in air conditioning is the vapor compression cycle. The four main components are:
In a direct expansion (DX) air conditioning system, the evaporator is placed directly in the air handling unit. In a chilled water system, the evaporator cools water (typically to 6.7 °C) which then circulates to the coils of air handling units.
Sensible heat calculation for an air flow rate:
Q sensible = 1.23 × flow rate (L/s) × ΔT (K)
Where 1.23 is the product of air density (1.2 kg/m³) and specific heat (1.026 kJ/kg·K), converted for flow rate units in L/s. This factor must be memorized.
Latent heat calculation:
Q latent = 3.0 × flow rate (L/s) × Δω (g/kg)
Where 3.0 is the latent heat of vaporization factor for water at room temperature (≈ 2500 kJ/kg) converted.
2. Applied Psychrometrics
2.1 The Psychrometric Chart
The psychrometric chart is the essential graphical tool for the air conditioning mechanic. It represents the thermodynamic properties of moist air at a given atmospheric pressure (typically 101.325 kPa at sea level). The main lines:
2.2 Fundamental Psychrometric Processes
| Process | Line on the Chart | Application |
|---|---|---|
| Sensible heating | Horizontal to the right | Heating coil |
| Sensible cooling | Horizontal to the left | Cooling coil (dry air) |
| Adiabatic humidification | Constant enthalpy line | Air washer, steam humidifier |
| Dehumidification by cooling | Curve downward and to the left | Cold coil with condensation |
| Mixing of two air streams | Straight line between the two points | Return air/outdoor air mixing |
Dew point: the temperature at which air becomes saturated (RH = 100 %) if cooled at constant pressure. It is the coil surface temperature below which condensation will occur.
Sensible Heat Factor (SHF):
SHF = Q sensible / (Q sensible + Q latent)
An SHF of 0.75 means that 75 % of the total heat load is sensible. This factor determines the slope of the condition line (or sensible heat factor line) on the psychrometric chart, which connects the return air point to the supply air point.
2.3 Typical Psychrometric Calculations for the Exam
Example 1 — Air Mixing:
You mix 600 L/s of return air at 24 °C DBT, 50 % RH with 200 L/s of outdoor air at 32 °C DBT, 60 % RH. The mixture temperature is:
DBT mixture = (600 × 24 + 200 × 32) / (600 + 200) = (14,400 + 6,400) / 800 = 26 °C
Example 2 — Dehumidification:
A coil cools 1,000 L/s of air from 26 °C DBT, 21 °C WBT to 12 °C DBT, 11 °C WBT. The amount of condensed water is:
Δω = ω₁ − ω₂ = 13.5 g/kg − 8.0 g/kg = 5.5 g/kg
Mass flow rate of air = 1,000 L/s × 1.2 kg/m³ / 1,000 = 1.2 kg/s
Condensed water = 1.2 kg/s × 5.5 g/kg = 6.6 g/s = 23.8 kg/h
Common trap: do not confuse the 1.23 factor (sensible heat) with the 3.0 factor (latent heat). Always check the units of the air flow rate.
3. Heat Load Calculations
3.1 Calculation Methodology
Heat load calculations follow the method from the ASHRAE Handbook — Fundamentals (RTS — Radiant Time Series method for cooling loads). For the exam, you must know the components of the load:
External sensible loads:
Internal sensible loads:
Latent loads:
3.2 Typical Thermal Transmission Coefficients (U)
| Element | Typical U value (W/m²·K) |
|---|---|
| Insulated exterior wall (R-20) | 0.30 |
| Insulated roof (R-30) | 0.20 |
| Double sealed glazing | 2.8 |
| Triple glazing with low-emissivity coating | 1.6 |
| Solid wood door | 2.2 |
Golden rule: the lower the U value, the better the insulation. Thermal resistance R = 1/U.
3.3 Ventilation and Indoor Air Quality
Standard ASHRAE 62.1 (Ventilation for Acceptable Indoor Air Quality) is the reference. For commercial buildings, the required outdoor air flow rate is calculated using the zone ventilation method:
Vbz = Rp × Pz + Ra × Az
Where:
Typical values for an office: Rp = 2.5 L/s·person, Ra = 0.3 L/s·m².
Minimum requirement: the National Building Code of Canada (NBC) requires a minimum of 8 L/s per person for spaces where occupants are sedentary, or 0.35 air changes per hour, whichever is greater.
4. Air Handling Systems
4.1 System Classification
| System Type | Distribution Fluid | Advantages | Disadvantages |
|---|---|---|---|
| All-air (constant volume) | Air | Good humidity control, centralized maintenance | Large ductwork |
| All-air (variable volume — VAV) | Air | Energy savings, individual control | Risk of stratification, need for reheat |
| Air-water (fan coils) | Air + water | Reduced ductwork, local control | Possible condensation, multiple maintenance points |
| All-water (fan coils) | Water | Very compact | No mechanical ventilation, freeze risk |
| Direct expansion (DX) | Refrigerant | Efficient, compact | Limited line lengths, limited humidity control |
4.2 The Air Handling Unit (AHU)
The air handling unit is the heart of the system. Its components, in air flow order:
Exam trap: the order of components is crucial. The cooling coil must be placed before the heating coil and after the filters. The humidifier is generally placed after the coils.
4.3 Fans
The two main families of fans:
Centrifugal fans:
Axial fans:
Fan Laws (at constant density):
Example: If the rotational speed increases by 10 %, the flow rate increases by 10 %, the pressure increases by 21 % (1.1² = 1.21), and the power increases by 33 % (1.1³ = 1.331). This is a classic exam trap.
4.4 Air Ducts
Sizing methods:
Pressure loss in ducts:
ΔP = f × (L/D) × (ρ × V² / 2)
Where f is the friction factor (dependent on Reynolds number and roughness), L the length, D the hydraulic diameter, ρ the density, and V the velocity.
Equivalent diameter for a rectangular duct:
De = 1.30 × [(a × b)⁵ / (a + b)²]^(1/8)
Where a and b are the dimensions of the rectangular duct in mm. This formula is used to use the pressure loss charts for circular ducts.
Recommended duct velocities:
| Application | Main duct (m/s) | Branch (m/s) |
|---|---|---|
| Residential | 3 to 4 | 2 to 3 |
| Commercial (quiet) | 5 to 6 | 3 to 4 |
| Commercial (standard) | 7 to 9 | 5 to 6 |
| Industrial | 10 to 13 | 7 to 10 |
5. Air Conditioning Equipment
5.1 Chilled Water Chillers
Chilled water chillers produce cold water (typically at 6.7 °C) to supply the coils of AHUs and fan coils. Two main types:
Air-cooled chillers:
Water-cooled chillers:
Coefficient of Performance (COP):
COP = Cooling capacity (kW) / Power input (kW)
EER (Energy Efficiency Ratio) = COP × 3.412 (in BTU/h per watt)
Exam trap: COP is dimensionless (kW/kW), while EER is in BTU/(h·W). Never confuse them.
5.2 Cooling Towers
The cooling tower rejects condenser heat to the atmosphere through evaporation. Types:
Operating parameters:
Example: Outdoor air at 28 °C DBT, 22 °C WBT. A tower with an approach of 4 °C will produce water at 26 °C. If the range is 6 °C, the hot water will enter at 32 °C.
Freeze consideration: in northern climates, cooling towers must be protected against freezing. Measures include: water bypass, basin heating, fan speed control, and automatic drain.
5.3 Evaporative Condensers
The evaporative condenser combines the condenser and cooling tower into a single unit. The refrigerant circulates directly through coils that are sprayed with water and swept by air. The evaporated water absorbs heat from the refrigerant. Advantages: compactness, high efficiency. Disadvantages: water quality maintenance, corrosion risk.
5.4 Rooftop Units (RTU)
Rooftop units (RTUs) are self-contained systems installed on the roof, containing the compressor, condenser, evaporator, fans, and filters in a single enclosure. They are factory-fabricated and only require electrical connection and ductwork. Typical capacities: from 3 to 100 tons of refrigeration.
1 ton of refrigeration = 12,000 BTU/h = 3.517 kW
6. Control and Regulation
6.1 Control Strategies
Temperature control in a chilled water system is achieved by:
Typical AHU control sequence:
6.2 Sensors
| Sensor | Measurement | Typical Accuracy |
|---|---|---|
| Thermistor | Temperature | ± 0.2 °C |
| RTD (Pt100) | Temperature | ± 0.1 °C |
| Capacitive humidity sensor | Relative humidity | ± 2 % |
| Differential pressure sensor | Pressure | ± 0.5 % of scale |
| Hot wire anemometer | Air velocity | ± 2 % |
6.3 Free Cooling Sequence
Free cooling (economizer) uses outdoor air to cool the building when its temperature is lower than the return air temperature. Two strategies:
The enthalpy economizer is more accurate because it accounts for humidity. The National Energy Code of Canada for Buildings (NECB) requires economizers on systems over 35 kW (10 tons) in most Canadian climates.
7. Commissioning and Troubleshooting
7.1 Commissioning Procedure
Commissioning is the process of verifying that all systems operate in accordance with specifications. Steps:
7.2 Common Troubleshooting
Symptom: insufficient air flow
Symptom: supply air temperature too high
Symptom: excessive humidity
7.3 Heat Balances
Cooling coil balance:
Q total = Q sensible + Q latent
Q total = mass flow rate of air × (h₁ − h₂)
Where h₁ and h₂ are the enthalpies of the air entering and leaving the coil.
Condenser balance:
Q condenser = Q evaporator + W compressor
This relationship is fundamental. If the compressor consumes 10 kW and the evaporator absorbs 40 kW, the condenser must reject 50 kW.
8. Applicable Canadian Codes and Standards
8.1 The Canadian Electrical Code (CE Code)
The Canadian Electrical Code, Part I (C22.1) applies to all electrical installations. Key points for air conditioning systems:
Exam trap: the CE Code requires an accessible disconnecting means within 3 m of the equipment for motors and air conditioning appliances (Rule 28-600).
8.2 The National Building Code of Canada (NBC)
The NBC (National Building Code of Canada) contains ventilation, fire safety, and energy efficiency requirements. Relevant sections:
8.3 The National Energy Code of Canada for Buildings (NECB)
The NECB (National Energy Code of Canada for Buildings) imposes energy efficiency requirements:
8.4 CSA Standard B52
Standard CSA B52 (Mechanical Refrigeration Code) governs the installation of refrigeration systems. Key points:
8.5 CSA Standard B149.1
Standard CSA B149.1 (Natural Gas and Propane Installation Code) applies to gas-fired heating systems that are part of air handling. Key points:
9. Energy Efficiency and Sustainability
9.1 Performance Indicators
| Indicator | Definition | Application |
|---|---|---|
| EER | BTU/h of cooling per watt consumed | DX units |
| COP | kW of cooling per kW consumed | Chillers, heat pumps |
| IPLV | Integrated Part Load Value — weighted efficiency at part load | Chillers |
| kW/ton | Power consumed per ton of refrigeration | Quick comparison |
| SCOP | Seasonal COP — seasonal efficiency | Heat pumps |
Typical values for the exam:
9.2 Heat Recovery
Heat recovery systems transfer energy from exhaust air to incoming outdoor air. Types:
Heat exchanger efficiency calculation:
ε = (T outdoor outlet − T outdoor inlet) / (T exhaust inlet − T outdoor inlet) × 100 %
Example: Outdoor air at −10 °C, exhaust air at 22 °C. The outdoor air leaves at 12 °C. Efficiency = (12 − (−10)) / (22 − (−10)) × 100 % = 22 / 32 × 100 % = 68.75 %.
10. Safety and Environment
10.1 Refrigerants and the Environment
Refrigerants are classified according to their GWP (Global Warming Potential) and ODP (Ozone Depletion Potential):
| Refrigerant | Type | GWP (100 years) | ODP | Status |
|---|---|---|---|---|
| R-22 | HCFC | 1,810 | 0.055 | Phase-out |
| R-410A | HFC | 2,088 | 0 | In transition |
| R-134a | HFC | 1,430 | 0 | In transition |
| R-32 | HFC | 675 | 0 | Accepted |
| R-454B | HFO | 466 | 0 | New |
| R-290 (propane) | HC | 3 | 0 | Flammable A3 |
| R-717 (ammonia) | Natural | 0 | 0 | Toxic B2 |
The Ozone-depleting Substances and Halocarbon Alternatives Regulations (Government of Canada) requires:
10.2 Risks Related to Air Handling Systems
10.3 Lockout/Tagout
Lockout/tagout is mandatory before any intervention on an air conditioning system. Procedure:
Traps to Avoid
Summary
This chapter has presented the essential knowledge to pass the "Air Conditioning and Air Handling Systems" section of the Red Seal exam. Here are the key points to remember:
For the exam, practice solving air mixing problems, coil heat balance calculations, and duct sizing. Speed and accuracy in these calculations make the difference between a passing grade and an excellent one.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free