Chapter VI

Piping, Fittings, and System Installation

Red Seal Practice study guide with diagrams.

Piping, Fittings, and System Installation

Chapter Introduction

This chapter covers all the knowledge required for the Red Seal exam concerning piping, fittings, and the installation of refrigeration and air conditioning systems. You must master materials, joining techniques, safety rules, expansion calculations, and the requirements of Canadian national standards. Mastering this content is essential, as questions on this topic typically represent 10 to 15% of the exam.

Piping Materials and Their Applications

Copper Tubing

Copper is the predominant material in refrigeration for liquid, suction, and discharge lines. You must know the three types of hardness:

TypeHardnessTypical Use
KSoft (annealed)Liquid lines, small systems
LMedium-hardSuction and discharge lines
MHardWater piping, rarely in refrigeration

Nominal copper tubing dimensions are based on the outside diameter (O.D.). Wall thickness varies by type (K, L, M), which affects the inside diameter (I.D.) and therefore the flow capacity. For refrigerant lines, Type L or K is generally used.

Rule of thumb: Refrigerant velocity in suction lines must be maintained between 4 and 10 m/s to ensure oil return. In liquid lines, velocity must be below 1.5 m/s to avoid noise and erosion.

Steel Pipe

Black steel (Schedule 40 or 80) is used for ammonia (NH₃) systems and for large R-22 or R-134a installations. Stainless steel is reserved for special applications (food industry, corrosive products).

The schedule indicates wall thickness. Schedule 80 has a thicker wall than Schedule 40 for the same nominal diameter. For ammonia, Schedule 80 is generally required for diameters under 2 inches.

Plastic and Other Materials

PVC: Only for condensate drains and vents. Never for refrigerant.
CPVC: High-temperature condensate drains.
PEX: Glycol water in closed-loop systems.
Galvanized steel: Prohibited for refrigerant lines (chemical reaction with oil).

Fittings and Joining Techniques

Brazed Fittings (Soldering)

Brazing uses a filler metal whose melting point is above 450 °C. In refrigeration, silver brazing is used with silver alloys (15%, 35%, or 45% silver).

Approximate melting temperatures:

15% silver alloy: 640 °C
35% silver alloy: 700 °C
45% silver alloy: 620 °C

Correct brazing procedure:

26.Cut the tube squarely with a tube cutter (never a hacksaw for copper).
27.Deburr the inside and outside of the tube.
28.Clean the surfaces with abrasive paper or a wire brush.
29.Apply flux (if required by the alloy) to the male tube only.
30.Insert the fitting and heat the fitting uniformly (not the tube directly).
31.Apply the filler rod when the fitting is at temperature.
32.Allow to cool naturally. Never quench in water.

Trap to avoid: Heating the tube directly instead of the fitting. The filler metal will be drawn toward the hottest zone, creating an incomplete joint.

Mechanical Fittings

Flare fittings: Used for small liquid lines (1/4", 3/8", 1/2"). The flare angle must be 45°. The flaring tool must be properly centered to avoid an asymmetrical flare.
Compression fittings: Used for small-diameter copper tubing, mainly in control systems (capillary tubes).
Threaded fittings (NPT): Tapered threads for steel. Sealing is ensured by thread sealant (Teflon tape or pipe joint compound). NPT threads have a 60° angle and a taper of 1/16 per inch.

Arc-Welded Fittings (Steel)

For steel, arc welding (SMAW) or TIG welding is used. TIG is preferred for ammonia because it produces a clean bead without slag. Full penetration is essential to avoid oil pockets and corrosion.

Thermal Expansion Calculations

The thermal expansion of copper is 0.0000167 m/m·°C (16.7 × 10⁻⁶ m/m·°C). For a 30-meter line with a ΔT of 50 °C:

ΔL = L₀ × α × ΔT

ΔL = 30 m × 0.0000167 /°C × 50 °C = 0.025 m = 25 mm

This 25 mm expansion must be absorbed by expansion loops or natural changes in direction. The minimum length of an expansion loop is calculated by:

L = 2 × √(3 × E × D × ΔL / S)

Where:

E = modulus of elasticity of copper (110,000 MPa)
D = outside diameter of the tube (mm)
ΔL = expansion (mm)
S = allowable stress (generally 70 MPa for copper)

Example: For a 28.6 mm O.D. tube with 25 mm of expansion:

L = 2 × √(3 × 110,000 × 28.6 × 25 / 70) = 2 × √(3,367,857) = 2 × 1835 = 3670 mm ≈ 3.7 m

Slopes and Oil Return

Recommended Slopes

Line TypeRecommended SlopeDirection
Horizontal suction line1/2 inch per 10 feet (4 mm/m)Toward the compressor
Horizontal liquid line1/4 inch per 10 feet (2 mm/m)Toward the expansion valve
Horizontal discharge line1/2 inch per 10 feet (4 mm/m)Toward the condenser

Oil Traps (Siphons)

An oil trap must be installed at the base of any riser in the suction or discharge line when the vertical height exceeds 2.5 meters. The general rule:

Riser height < 2.5 m: no trap required
Riser height > 2.5 m: trap at the base
Riser height > 7.5 m: traps at the base and midpoint (every 4 to 5 meters)

Important: In variable-capacity systems (variable-speed compressors), double traps or double-rise traps are sometimes necessary to ensure oil return at low flow rates.

Pipe Insulation and Protection

Types of Insulation

MaterialTemperature RangeUse
Cellular rubber (Armaflex)-40 °C to +105 °CSuction and liquid lines
Fiberglass-50 °C to +450 °CHot piping, steam
Extruded polystyrene-50 °C to +75 °CRefrigerated piping
Polyurethane foam-60 °C to +100 °CLow-temperature piping

Minimum thickness: Suction line insulation must be thick enough to prevent condensation. The rule of thumb: for a surface temperature of -10 °C and 60% relative humidity at 24 °C, at least 25 mm of cellular rubber is required.

Vapor Barrier

The vapor barrier is mandatory on the outer surface of insulation on cold lines. It prevents moisture vapor from migrating toward the cold surface. Vapor barrier joints must be sealed with an appropriate adhesive. A tear in the vapor barrier negates the effectiveness of the insulation.

Supports and Anchors

Support Spacing

Tube Diameter (O.D.)Horizontal SpacingVertical Spacing
1/4" to 3/8" (6-10 mm)1.2 m1.8 m
1/2" to 7/8" (12-22 mm)1.8 m2.4 m
1-1/8" to 2-1/8" (28-54 mm)2.4 m3.0 m
2-5/8" and larger (67 mm+)3.0 m3.6 m

Important rule: Supports must never compress the insulation. Use clamps with insulating inserts or double-shell supports. Rigid supports (without insulation) create thermal bridges that cause condensation.

Fixed Anchors

Fixed anchors (anchor points) divide the piping into independent expansion sections. They must be placed:

Near heavy equipment (compressors, condensers)
At changes in direction
On either side of main valves

Canadian Electrical Code, Part I Requirements

The Canadian Electrical Code, Part I (C22.1-21) governs the electrical installation of refrigeration systems. The relevant rules for piping:

Rule 8-200 (Section 8): Conductor Sizing

The ampacity of conductors must be determined according to the Code tables. For compressors, the conductor must be sized at 125% of the full-load current (FLA).

Rule 26-252: Motor Disconnection and Protection

Each motor must have an accessible disconnecting means and overload protection. The disconnecting means must be visible or lockable.

Rule 28-110: Overcurrent Protection

The circuit breaker or fuses must be sized according to the motor's starting current. For a hermetic compressor, use the rated load current (RLA) and not the FLA.

Trap to avoid: Confusing RLA (Running Load Amps) and FLA (Full Load Amps). RLA is used for sizing overload protection, while FLA is used for sizing conductors.

CSA B149.1 Code (Natural Gas and Propane)

CSA B149.1 applies to gas heating systems, but also to refrigeration installations using gas burners. Key points:

Article 5.4.1: Gas piping must be supported at intervals not exceeding 3 meters.
Article 5.8.2: Gas piping fittings must be accessible for inspection.
Article 6.2.1: The test pressure must be 1.5 times the service pressure, with a minimum of 350 kPa (50 psi) for low-pressure systems.

CSA Standards for Refrigeration Piping

CSA B52 (Mechanical Refrigeration Code)

CSA B52 is the reference standard for the installation of refrigeration systems in Canada. Essential points:

Article 4.2.1: Piping must conform to design specifications and be protected against mechanical damage.
Article 4.3.2: Piping passing through walls, floors, or roofs must be protected by sleeves.
Article 4.4.1: Shut-off valves must be installed in accessible locations.
Article 5.1.1: Pressure tests must be performed in accordance with the requirements of the standard.

Pressure Testing per CSA B52

Test TypePressureDurationCriterion
Strength test1.5 × service pressure15 minutesNo leaks
Tightness testService pressure30 minutesNo pressure drop
Refrigerant testService pressure with refrigerant1 hourElectronic detection

Nitrogen test procedure:

101.Pressurize to 10% of the test pressure (maximum 100 kPa) and wait 5 minutes.
102.Increase in 10% increments up to the final test pressure.
103.Maintain the pressure for a minimum of 15 minutes.
104.Check joints with a soap solution.

Important: Never use oxygen or acetylene for pressure tests. Use only dry nitrogen or CO₂.

Installation of Valves and Accessories

Service Valves

Service valves (Schrader valves) must be installed:

At the compressor inlet and outlet
At the expansion valve inlet
At the condenser outlet
On each side of the filter-drier

Filter-Driers

The filter-drier must be installed in the liquid line, between the condenser and the expansion valve. It must be:

Accessible for replacement
Installed with a shut-off valve on each side
Oriented in the direction of flow (arrow on the body)

Sight Glasses

The sight glass must be installed in the liquid line, after the filter-drier. A sight glass full of clear liquid indicates a correct charge. Bubbles indicate a refrigerant shortage or excessive pressure drop.

Welding and Safety

Personal Protective Equipment (PPE)

Safety glasses with face shield for brazing
Heat-resistant leather gloves
Flame-resistant clothing
Respiratory protection if ventilation is insufficient

Ventilation

Brazing copper produces zinc oxide fumes and cadmium fumes (if the alloy contains it). Adequate ventilation is mandatory. Cadmium-free alloys are preferred for health reasons.

Fire Risk

Keep combustible materials at least 3 meters away
Use a fire-resistant screen when brazing near flammable surfaces
Have a fire extinguisher within reach
Never braze a tube containing refrigerant under pressure

Complete Installation Procedures

Suction Line Installation

135.Sizing: Choose the diameter according to the compressor manufacturer's tables. A line that is too small increases pressure drop and reduces capacity. A line that is too large reduces velocity and prevents oil return.
136.Slope: Install with a slope of 4 mm/m toward the compressor.
137.Oil traps: Install at the base of risers.
138.Insulation: Insulate the entire line with the calculated thickness.
139.Supports: Space according to the previous table.
140.Tightness test: Pressurize to the test pressure.

Liquid Line Installation

142.Sizing: The total pressure drop (friction + static) must not exceed the equivalent of 1 °C of saturation. For R-134a, this represents approximately 30 kPa.
143.Subcooling: A subcooling of 4 to 6 °C is recommended to avoid flash gas in the liquid line.
144.Liquid riser: For each meter of height, static pressure increases by approximately 10 kPa (for R-134a). A 10-meter riser adds 100 kPa, which can cause flash gas.
145.Valves: Install a shut-off valve at the expansion valve inlet.

Discharge Line Installation

147.Slope: Toward the condenser to facilitate oil drainage.
148.Traps: At the base of risers.
149.Insulation: Not required for efficiency, but sometimes necessary for personnel protection (surface temperature > 60 °C).

Pressure Drop Calculations

Pressure Drop in Refrigerant Lines

The total pressure drop (ΔP) in a line consists of:

Friction loss (depends on diameter, length, roughness)
Static loss (depends on height and fluid density)

Simplified formula for static loss:

ΔP_static = ρ × g × h

Where:

ρ = density of the liquid refrigerant (kg/m³)
g = 9.81 m/s²
h = height (m)

Example: Liquid R-134a (ρ = 1200 kg/m³) in an 8-meter riser:

ΔP = 1200 × 9.81 × 8 = 94,176 Pa ≈ 94 kPa

This 94 kPa loss corresponds to approximately 3 °C of saturation for R-134a. It is too high and requires additional subcooling or a larger diameter.

Equivalent Length of Fittings

Each fitting adds an equivalent length of straight tubing. Typical values in equivalent diameters:

FittingEquivalent Length (in diameters)
90° elbow30 D
45° elbow16 D
Tee (straight through)20 D
Tee (branch)60 D
Open ball valve3 D
Open needle valve340 D

Example: A 90° elbow on a 28.6 mm O.D. tube is equivalent to 30 × 28.6 = 858 mm of straight tubing.

System Purging and Dehydration

Nitrogen Purging During Brazing

When brazing copper lines, a nitrogen purge (flow of 0.5 to 1 L/min) must be maintained inside the tube to prevent the formation of copper oxide (black scale). This oxidation forms at high temperatures and can clog expansion valves and damage compressors.

Vacuum Dehydration

After installation and the tightness test, the system must be dehydrated under vacuum:

173.Connect a vacuum pump (capacity ≥ 100 L/min) to the service valves.
174.Open all system valves.
175.Pull the vacuum down to 500 microns (0.5 Torr) or less.
176.Maintain the vacuum for a minimum of 30 minutes.
177.Vacuum hold test: Close the pump and verify that the pressure does not rise above 1000 microns within 10 minutes.

Micron: Unit of pressure used in dehydration. 1 micron = 0.001 Torr = 0.133 Pa. Standard atmosphere = 760,000 microns.

Triple Evacuation Method

For systems containing moisture, triple evacuation is recommended:

181.First vacuum down to 2000 microns.
182.Break the vacuum with dry nitrogen up to 0 kPa (atmospheric pressure).
183.Second vacuum down to 1500 microns.
184.Break the vacuum with nitrogen.
185.Third vacuum down to 500 microns or less.

This method is more effective than a single vacuum because it removes moisture by successive dilution.

Specific Safety Rules

Refrigerant Handling

Never heat a refrigerant cylinder above 52 °C.
Use a pressure regulator on refrigerant cylinders.
Wear safety glasses and gloves when handling.
Check the cylinder pressure before connecting.

Confined Space Work

Check oxygen concentration (minimum 19.5%).
Use a refrigerant detector.
Have a rescue plan.

Cutting and Opening Circuits

Before cutting a tube containing refrigerant:

199.Recover the refrigerant with a recovery machine.
200.Purge with nitrogen.
201.Verify the absence of pressure.
202.Cut with a tube cutter or saw (never with a flame).

Traps to Avoid

204.Confusing copper types: Type M is thinner than Type L. Using Type M for a refrigerant line can cause fatigue failure.
205.Forgetting the nitrogen purge during brazing: Internal oxidation destroys the system.
206.Sizing a suction line too large: Gas velocity becomes insufficient and oil does not return to the compressor.
207.Neglecting oil traps on risers over 2.5 meters.
208.Using a non-silver brazing alloy for refrigerant lines: Joints can crack under vibration.
209.Quenching a brazed joint in water: This creates micro-cracks.
210.Not accounting for thermal expansion: Uncompensated lines deform and leak.
211.Installing the filter-drier backwards: The direction of flow is indicated by an arrow.
212.Pulling the vacuum too quickly: Moisture freezes in the piping and does not evaporate.
213.Using a low-pressure gauge for a high-pressure test: Risk of gauge burst.
214.Forgetting the vapor barrier on cold line insulation: Condensation and water damage.
215.Confusing RLA and FLA for sizing electrical protections.
216.Installing a shut-off valve in a suction line without a service port: Makes diagnostics impossible.
217.Not checking material compatibility with the refrigerant (e.g., neoprene seals with R-1234yf).

Summary

Type L copper is the standard material for refrigerant lines. Schedule 80 steel is required for ammonia.
Silver brazing with silver alloy (15-45%) is the preferred joining method. Heat the fitting, never the tube directly.
The thermal expansion of copper is 0.0000167 m/m·°C. Expansion loops are necessary for long lines.
Slopes for horizontal lines: suction and discharge toward the compressor/condenser (4 mm/m), liquid toward the expansion valve (2 mm/m).
Oil traps are mandatory at the base of risers over 2.5 meters.
The pressure test is done with dry nitrogen, in stages, up to 1.5 times the service pressure.
Vacuum dehydration must reach 500 microns and hold the vacuum (no more than 1000 microns in 10 minutes).
CSA B52 is the reference standard for installation. The Canadian Electrical Code, Part I governs electrical aspects (Rules 8-200, 26-252, 28-110).
The nitrogen purge during brazing is mandatory to prevent internal oxidation.
Supports must be spaced according to tube diameter and must never compress the insulation.

Final Exam Tips

Memorize the key numerical values: slopes, spacings, melting temperatures, test pressures.
For calculation questions, first identify the appropriate formula, then check the units (meters vs. millimeters).
Questions on oil traps and slopes are very common. Review these sections before the exam.
Know the difference between soft soldering and brazing, and the associated temperatures.
For standards questions, remember the main CSA B52 article numbers and the Electrical Code rules mentioned in this chapter.

Good luck with your Red Seal exam preparation. Mastering piping is fundamental to passing the exam and to your career as a refrigeration and air conditioning mechanic.

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free