Chapter IV

Conductors, Cables, and Raceways

Red Seal Practice study guide with diagrams.

Conductors, Cables, and Raceways

Introduction

This chapter covers one of the most heavily tested areas on the Red Seal exam for construction electrician(s): conductors, cables, and raceways. You must master conductor types, their ampacities, service temperatures, correction factors, as well as the installation rules for raceways (conduits, wireways, cable trays). Questions cover both theory and practical calculations. An ampacity calculation error or a wrong cable type choice can cost you valuable points.

Fundamental Definitions

Conductor

A conductor is a wire or group of wires intended to carry electric current. In Canada, conductors are manufactured in copper or aluminum, in accordance with CSA C22.2 standards (series of standards for conductors). Copper is the most common material due to its high conductivity and corrosion resistance. Aluminum is used for larger sizes to reduce weight and cost, but it requires special precautions at connections (antioxidant paste, specific torque values).

Cable

A cable is an assembly of insulated conductors, with or without a protective sheath. Cables are classified according to their type (NMD90, NMWU, TECK90, ACWU, etc.) and their intended use. The outer sheath protects the conductors against mechanical damage, moisture, and chemical agents.

Raceway

A raceway is a closed or semi-closed system that contains and protects conductors. Raceways include conduits (EMT, PVC, rigid steel, etc.), wireways, cable trays, and cellular floors. The choice of raceway depends on the installation environment (indoor, outdoor, wet, corrosive, risk of mechanical damage).

Types of Conductors and Cables

Bare and Insulated Conductors

Bare conductors are used for grounding and bonding. Insulated conductors are covered with one or more layers of thermoplastic or thermosetting insulation. Common insulations include:

PVC (polyvinyl chloride): thermoplastic, moisture-resistant, used for TW, TWH, RW90 conductors.
XLPE (cross-linked polyethylene): thermosetting, heat-resistant, used for XHHW, RW90 conductors.
Nylon: used as an outer jacket to protect the primary insulation (THHN, THWN conductors).

Single-Conductor and Multi-Conductor Cables

Single-conductor cables (one insulated conductor) are used in conduits. Multi-conductor cables (several conductors under a common sheath) are used for residential, commercial, and industrial installations.

Armoured and Unarmoured Cables

Armoured cables (TECK90, ACWU) have a metallic armour that protects the conductors against mechanical damage. Unarmoured cables (NMD90, NMWU) are used in locations where the risk of damage is low.

Comparison Table of Common Cables

Cable TypeConductorsSheathTypical UseCode (Rule)
NMD90Copper, PVC insulatedNon-metallic PVC sheathResidential, indoor, dryRule 12-500
NMWUCopper, PVC insulatedMoisture-resistant PVC sheathBuried, outdoor, wetRule 12-500
TECK90Copper, XLPE insulatedInterlocked steel armour, PVC sheathIndustrial, outdoor, wetRule 12-604
ACWUAluminum or copper, XLPE insulatedAluminum armour, PVC sheathBuried, outdoorRule 12-604
AC90Copper, PVC insulatedInterlocked steel armourIndoor, dry, embeddedRule 12-600
NMD7Copper, PVC insulatedPVC sheathResidential, indoor, dryRule 12-500

Ampacity of Conductors

Definition

Ampacity is the maximum current a conductor can carry continuously without exceeding its maximum service temperature. Ampacity depends on:

The conductor size (AWG or kcmil).
The conductor material (copper or aluminum).
The insulation type and its service temperature.
The ambient temperature.
The number of conductors in the raceway (grouping factor).
The installation method (conduit, cable tray, buried, etc.).

Service Temperatures

The maximum service temperatures of insulations are standardized:

60 °C: TW, TWH insulations (older).
75 °C: THWN, XHHW, RW90 insulations.
90 °C: THHN, XHHW-2, RW90 insulations (for ampacities, but terminations often limit to 75 °C).

Important: The ampacity of a conductor is determined by the service temperature of its insulation, but connections to equipment terminals are often limited to 75 °C. If the terminal is marked 75 °C, you must use the 75 °C ampacity, even if the insulation is rated 90 °C.

Ampacity Table (excerpt from the Canadian Electrical Code, Part I, Chapter V, Table 2)

Table 2 of the Code gives ampacities for copper and aluminum conductors, at 75 °C, for different installation methods. Here is an excerpt for copper conductors:

Size (AWG/kcmil)Ampacity at 75 °C (A)Ampacity at 90 °C (A)
14 AWG1515
12 AWG2020
10 AWG3030
8 AWG5055
6 AWG6575
4 AWG8595
2 AWG115130
1 AWG130145
1/0 AWG150170
2/0 AWG175195
3/0 AWG200225
4/0 AWG230260
250 kcmil255290
350 kcmil310350
500 kcmil380430

Note: These values are for conductors in a conduit, with an ambient temperature of 30 °C. For other temperatures, apply the correction factors from Table 5A.

Correction Factors

Ambient Temperature

If the ambient temperature exceeds 30 °C, the ampacity must be reduced. Use Table 5A of the Code. For example, for an ambient temperature of 40 °C, the correction factor is 0.88 for 75 °C insulation, and 0.91 for 90 °C insulation.

Calculation: Corrected ampacity = Base ampacity × Temperature factor.

Grouping of Conductors

When more than three current-carrying conductors are in the same conduit, the ampacity must be reduced. Use Table 5C of the Code. For example:

Number of ConductorsCorrection Factor
4 to 60.80
7 to 90.70
10 to 200.50
21 to 300.45
31 to 400.40
41 and more0.35

Important: The neutral conductor is counted as a current-carrying conductor if it carries unbalanced current (for example, in a three-phase circuit with a shared neutral). In a single-phase 120/240 V circuit, the neutral is considered current-carrying.

Ampacity Calculation: Complete Example

Problem: You must install 6 copper conductors, size 4 AWG, THHN insulated (90 °C), in an EMT conduit, in a location where the ambient temperature is 40 °C. What is the maximum allowable current?

Solution:

53.Base ampacity at 90 °C for 4 AWG copper: 95 A (Table 2).
54.Correction factor for 40 °C ambient temperature with 90 °C insulation: 0.91 (Table 5A).
55.Correction factor for grouping of 6 conductors: 0.80 (Table 5C).
56.Corrected ampacity = 95 × 0.91 × 0.80 = 69.16 A.

Answer: The maximum ampacity is 69 A (rounded down).

Trap: Don't forget that if the equipment terminals are rated 75 °C, you must use the 75 °C ampacity as the base. In our example, the 75 °C ampacity for 4 AWG is 85 A. Corrected: 85 × 0.88 × 0.80 = 59.84 A. The actual ampacity would therefore be 59 A.

Voltage Drop

Principle

Voltage drop is the decrease in voltage between the source and the load, caused by the resistance of the conductor. Excessive voltage drop can cause poor equipment operation. The Canadian Electrical Code, Part I recommends a maximum voltage drop of 3% for lighting and heating circuits, and 5% for motor circuits (Rule 8-200, note).

Calculation Formula

For a single-phase circuit:

Voltage drop (V) = 2 × L × I × R / 1000

Where:

L = length of the conductor in meters (round trip).
I = current in amperes.
R = resistance of the conductor in ohms per 1000 meters (Table D1 of the Code).

For a three-phase circuit:

Voltage drop (V) = √3 × L × I × R / 1000

Typical Resistances (copper, at 75 °C)

Size (AWG)Resistance (Ω/1000 m)
1410.2
126.4
104.0
82.5
61.6
41.0
20.63
1/00.40

Voltage Drop Calculation Example

Problem: A single-phase 120 V circuit supplies a 15 A load at a distance of 50 m. You use 10 AWG copper conductors. What is the voltage drop in volts and as a percentage?

Solution:

76.Resistance of 10 AWG: 4.0 Ω/1000 m.
77.Voltage drop = 2 × 50 × 15 × 4.0 / 1000 = 6 V.
78.Percentage: 6 / 120 × 100 = 5%.

Answer: The voltage drop is 5%, which exceeds the 3% recommendation for lighting. You would need to increase the size to 8 AWG or reduce the distance.

Raceways: Conduits, Wireways, and Cable Trays

Types of Conduits

Conduit TypeAbbreviationMaterialTypical UseRule
Rigid metal conduitRMCGalvanized steelOutdoor, industrial, areas with mechanical riskRule 12-100
Electrical metallic tubingEMTThin-wall steelIndoor, commercial, residentialRule 12-100
Flexible metal conduitFMCSpiraled steelConnections to motors, vibration areasRule 12-100
PVC conduitPVCPolyvinyl chlorideBuried, outdoor, corrosiveRule 12-100
Rigid aluminum conduitRACAluminumOutdoor, corrosive areasRule 12-100

Conduit Fill

The maximum number of conductors in a conduit is limited to prevent overheating and facilitate pulling. The Code (Rule 12-1014) specifies fill percentages:

One conductor: 53% of the interior cross-section.
Two conductors: 31%.
Three conductors or more: 40%.

Calculation: The total cross-sectional area of the conductors (including insulation) must not exceed the allowable percentage of the interior cross-section of the conduit.

Conduit Dimensions Table (excerpt)

Nominal Size (inches)Interior Diameter (mm)Interior Area (mm²)
1/216.0201
3/421.0346
127.0572
1 1/435.0962
1 1/241.01320
253.02206

Cable Trays

Cable trays (or cable ladders) are open supports used to support cables in industrial and commercial installations. They allow more efficient heat dissipation than closed conduits. Installation rules are given in Rule 12-2200 and following.

Advantages:

Ease of installation and modification.
Better heat dissipation.
Easy access for maintenance.

Disadvantages:

Limited mechanical protection.
Requires adequate support.

Conductor Installation Rules

Rule 12-100: Scope

Rule 12-100 establishes the general requirements for the installation of conductors and raceways. Conductors must be installed in raceways or cables, except for specific exceptions (grounding, bare conductors, etc.).

Rule 12-108: Continuity of Raceways

Raceways must be continuous between boxes, devices, or panels. Joints must be mechanically strong and electrically continuous.

Rule 12-110: Supports for Raceways

Raceways must be supported at regular intervals to avoid mechanical stress. Maximum distances between supports are specified in Table 12-110:

Conduit TypeMaximum Distance Between Supports
EMT (horizontal)1.5 m
EMT (vertical)2.5 m
RMC (horizontal)2.5 m
RMC (vertical)3.0 m
PVC (horizontal)1.2 m
PVC (vertical)1.8 m

Rule 12-140: Identification of Conductors

Conductors must be identified by their colour or by markings. The grounding conductor must be green or green with a yellow stripe. The neutral conductor must be white or grey. Phase conductors can be black, red, blue, etc., depending on the system.

Rule 12-3000: Cables

Cables must be installed in accordance with the specific rules for their type. For example, NMD90 cables must be supported at maximum intervals of 1.4 m (Rule 12-510). TECK90 cables can be installed in wet locations or exposed to mechanical damage (Rule 12-604).

Minimum Conductor Size Calculations

General Method

The minimum size of a conductor is determined by:

115.The design current of the load (calculated according to the rules of Section 8 of the Code).
116.The ampacity of the conductor (Table 2, with correction factors).
117.The maximum allowable voltage drop.
118.Overcurrent protection requirements (Rule 14-100).

Complete Example

Problem: A three-phase 10 HP, 208 V motor has a full-load current of 30 A. The circuit is 40 m long. The conductors are copper, THHN insulated, in an EMT conduit, with an ambient temperature of 35 °C. Determine the minimum conductor size.

Solution:

122.Design current: 30 A × 1.25 (motor factor, Rule 28-106) = 37.5 A.
123.Required ampacity at 90 °C: 37.5 A. Table 2 indicates that 8 AWG (55 A at 90 °C) is sufficient.
124.Correction factor for 35 °C ambient temperature with 90 °C insulation: 0.96 (Table 5A).
125.Corrected ampacity: 55 × 0.96 = 52.8 A. This is greater than 37.5 A, so 8 AWG is acceptable.
126.Voltage drop check: R for 8 AWG = 2.5 Ω/1000 m. Voltage drop = √3 × 40 × 37.5 × 2.5 / 1000 = 6.5 V. Percentage: 6.5 / 208 × 100 = 3.1%. This is acceptable (less than 5% for motor circuits).

Answer: Use 8 AWG copper, THHN conductors.

Traps to Avoid

129.Confusing service temperatures: Don't base your ampacity calculation on 90 °C if the terminals are rated 75 °C. Always use the lower temperature.
130.Forgetting correction factors: Temperature and grouping factors are cumulative. Multiply them together.
131.Not counting the neutral in grouping: In a three-phase circuit with a shared neutral, the neutral is current-carrying and must be counted.
132.Confusing cable types: NMD90 is for dry indoor locations, NMWU for wet outdoor locations, TECK90 for industrial. Read the question carefully.
133.Using the wrong voltage drop formula: Single-phase: 2 × L × I × R / 1000. Three-phase: √3 × L × I × R / 1000.
134.Forgetting the 1.25 factor for motors: The design current of a motor is the full-load current × 1.25.
135.Ignoring raceway support requirements: Maximum distances between supports are specific to each conduit type.
136.Not checking conduit fill: The maximum fill percentage is 40% for three conductors or more.

Summary

Conductors are copper or aluminum, with insulations rated at 60 °C, 75 °C, or 90 °C.
Ampacity is determined by Table 2 of the Code, with correction factors for ambient temperature (Table 5A) and grouping (Table 5C).
The maximum recommended voltage drop is 3% for lighting and 5% for motor circuits.
Raceways include conduits (EMT, RMC, PVC, etc.), wireways, and cable trays.
The maximum conduit fill is 40% for three conductors or more.
Cables are classified according to their type (NMD90, NMWU, TECK90, ACWU) and their use.
Rules 12-100 to 12-3000 of the Canadian Electrical Code, Part I, Chapter V, govern the installation of conductors and raceways.
Motors require a 1.25 factor on the full-load current to determine the design current.
Grounding conductors are green or green with a yellow stripe; neutrals are white or grey.

Traps to Avoid (Reminder)

Never confuse ampacities at 75 °C and 90 °C.
Always apply temperature and grouping correction factors.
Check voltage drop for long circuits.
Use the correct formula (single-phase vs. three-phase).
Respect raceway support requirements.
Count the neutral as a current-carrying conductor in three-phase circuits with a shared neutral.

Exam Tips

Memorize common ampacities (14, 12, 10, 8, 6, 4, 2 AWG) for copper at 75 °C and 90 °C.
Learn the most common correction factors (40 °C temperature, grouping of 4 to 6 conductors).
Practice calculating voltage drop with varied examples.
Read questions carefully to identify the cable type, ambient temperature, and number of conductors.
Use the Canadian Electrical Code, Part I, Chapter V as your primary reference. Rule numbers are often cited in the questions.

This chapter gives you a solid foundation to tackle questions on conductors, cables, and raceways on the Red Seal exam. Review the Code tables, practice the calculations, and stay methodical in your answers.

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free